Electric wiring

Installation Procedure

Electric wiring

 

 

8. Electric wiring

WARNING!

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER

SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.

GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING

LINE VOLTAGE CONNECTIONS.

(1)Selection of size of power supply and interconnecting wires. Precautions for Electric wiring

8. Electric wiring Electric wiring work should be conducted only by authorized personnel.

Manual background Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.

Manual background Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)

Item

 

Circuit

breaker

Power source

Earth leakage breaker

Model

Phase

Switch breaker

Overcurrent protector

wire size

Switch

Leak

 

(A)

rated capacity (A)

(minimum)

breaker

current

AU122AEERA

1

40

26

2.5mm2

40A

30mA

AU182AFERA

 

 

 

 

 

 

 

 

 

 

 

 

 

AU242AGERA

 

 

 

 

 

 

AU282AHERA

1

60

40

4.0mm2

60A

30mA

AU362AHERA

 

 

 

 

 

 

AU422AIERA

1

60

40

6.0mm2

60A

30mA

AU522AIERA

 

 

 

 

 

 

AU36NAHERA

3

30

20

2.5mm2

30A

30mA

AU42NAIERA

 

 

 

 

 

 

AU52NAIERA

3

30

20

4.0mm2

30A

30mA

Manual background If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.

Manual background If the fuse of control box is broken, please change it with the type of T25A/450VAC; if the fuse of control PC board is broken, please change it with the type of T3.15A/250VAC.

Manual background The wiring method should be in line with the local wiring standard.

Manual background The power cable and connecting cable should be self-provided.

For AU122AEERA,AU182AFERA, the power cable should be H05RN-F 3G 2.5mm2.

For AU242AGERA, AU282/362AHERA, the power cable should be H05RN-F 3G 4.0mm2 For AU422/522AIERA, the power cable should be H05RN-F 3G 6.0mm2

For AU36NAHERA, AU42NAIERA the power cable should be H07RN-F 5G 2.5mm2 For AU52NAIERA, the power cable should be H07RN-F 5G 4.0mm2.

Manual background The connecting cable should be H05RN-F 4G 0.75mm2.

All the cables shall have got the European authentication certificate. During installation, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.

Manual background The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should not be no less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.

Manual background The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the diameter of the wire should be enlarged according to the local wiring standard.

Manual background A leakage breaker must be installed.