Limitations on the installation

3. Limitations values on the piping work .

L1

A

L2

L3

L4

h

B

H +

C

H -

D

The piping length information, please refer the following table.

Item

Unit

Descriptions

 

Standard

Maximum

 

A, B, C,D liquid pipe

mm

Size of the liquid side connection pipe

 

6.35

/

A, B, C,D Gas pipe

mm

Size of the gas side connection pipe

 

9.52

/

 

 

 

 

 

 

 

L1

(one way)

m

Pipe length when the compressor connects with two indoor units

 

10

25

 

 

 

 

 

 

 

L2

(one way)

m

Pipe length when the compressor connects with two indoor units

 

10

25

 

 

 

 

 

 

 

L3

(one way)

m

Pipe length when the compressor connects only one indoor unit

 

10

25

 

 

 

 

 

 

 

L4

(one way)

m

Pipe length when the compressor connects only one indoor unit

 

10

25

 

 

 

 

 

 

L1+L2+L3+L4

m

Total liquid piping length(It is no need to charge additional

 

40

60

 

 

 

refrigerant within this value)

 

 

 

h

 

m

Drop between every two indoor units

 

1

5

 

 

 

 

 

 

 

H +

 

m

Drop between the outdoor unit and the indoor unit

 

5

15

H -

 

m

Drop between the outdoor unit and the indoor unit

 

5

10

9

Page 11
Image 11
Haier AU342XHERA, AU282XHERA installation manual Descriptions Standard Maximum