Installation Procedure

Electric wiring

For: AU182AEEAA

OUTDOOR UNIT

TERMINAL BLOCK

To Indoor Unit

1 2 3

Y/G

FIG.1

For :, AU242AGEAA, AU282AHEAA, AU362AIEAA

L N

POWER SUPPLY: 1PH, 220-230V~, 50Hz

To Indoor Unit

1

2

Y/G

3

OUTDOOR UNIT

TERMINAL BLOCK

FIG.2

For: AU28NAHEAA, AU36NAIEAA, AU48NAIEAA, AU60NAIEAA

To Indoor Unit

R S T

Y/G

N 1 2 3

OUTDOOR UNIT TERMINAL BLOCK

POWER SUPPLY:

 

380-400V, 3N~, 50Hz

FIG.3

 

WARNING

DO NOT CONNECT THE NEUTRAL WIRE N TO R , S OR T PHASE. INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG.1 FIG.2 FIG.3.INCORRECT WIRING CAUSE EQUIPMENT DAMAGE.

(3)Wiring procedure

1)Remove set screws on the side before taking off the front panel toward the direction shown in figure.

2)Connect wires to the terminal block correctly and fix the wires with a wire clamp equipped nearby the terminal block.

3)Route the wires in a proper way and penetrate the wires through the opening for electric wiring on the side panel.

12

Page 13
Image 13