Haier 0010571564, AU422BIBAA operation manual Electric wiring

Models: 0010571564 AU422BIBAA

1 16
Download 16 pages 44.86 Kb
Page 9
Image 9
Electric wiring

Electric wiring

Manual background Warning

Manual background The wiring work should commissioned to a qualified worker according to the installation manual to perform. The air conditioner must use special power circuit. Insufficient power capacity or improper work may cause electric shock and fire.

Manual background When wiring, the power cable must use the specified cable to firmly connect and fix. Do not let the external force of the cable transfer to the terminal block. Improper connection or fixation may cause heat and fire, etc. accident.

Manual background Must connect with grounding wire.Manual background Connect with grounding wire as specified. Unreliable grounding may lead to electric shock. Do not connect the grounding wire on the gas pipe, city water pipe, lightning rod or telephone line.Manual backgroundManual background Use the fuse with proper specification. Do not use wire or any other material to replace fuse, otherwise it may cause damage of unit or fire. Manual background

Manual background Notice

Manual background The Creepage breaker must be installed.

If not installing Creepage breaker may easily cause electric shock. After wiring, please power on the unit to detect electricity leakage.

Manual background If the power cable is damaged, in order to avoid danger, it must be changed by the manufacturer or its repair center or the similar professional personnel. For the power cable of indoor unit, please mate it according to the manual of indoor unit.

Manual background Avoid the electric wire touching the high temperature part of the connection pipe, in order not to the insulation part of the cable be melted causing accidents.

Manual background After connecting to the terminal block, the connection wire should be bent to a U-shaped bend and use wire presser to fix.

Manual background Before performing vacuumizing the refrigerant pipe system, do not power on the outdoor unit,

Manual background The power cable of indoor unit and the connection wire of indoor and outdoor unit should be complied with what the operation manual of indoor unit specified.

Manual background The connection of power cable should be complied with the local wiring regulations.

Manual background When wiring on site, choose the specification of wire and creepage breaker as follows:

 

The minimum section area of wire

Knife switch

 

Power supply

(mm2) (the connection wire of metal

(A)

 

Creepage breaker

pipe and synthetic resin pipe )

 

 

 

Below 20m

Below 50m

Capacity

Fuse

 

 

 

 

 

 

 

1PH, 220V, 50Hz

10

16

40

40

40A, 100mA, below 0.1s

 

 

 

 

 

 

7

Page 9
Image 9
Haier 0010571564, AU422BIBAA operation manual Electric wiring