English

1.Only rigid metal duct work should be used.

2.Venting vertically through a roof may expose the exhaust system to down drafts causing an increase in vent restriction.

3.Running the exhaust system through an uninsulated area may cause condensation and faster accumulation of lint.

4.Compression of crimping of the exhaust system will cause an increase in vent restriction.

5.In Canada, that only those foil-types flexible ducts, if any, specifically identified for use with the appliance by the manufacturer shall be used. In the United States, that only those foil-type flexible ducts, if any, specifically identified for use with the appliance by the manufacturer and that comply with the UL Outline for Clothes Dryer Transition Duct, Subject 2158A (2006), shall be used.

6.In Canada, that the exhaust duct shall be 102mm in diameter. In the United States, the required exhaust duct diameter.

7.The total length of flexible metal duct shall not exceed 2.4m.

The exhaust system should be inspected and cleaned a minimum of every 12 months with normal usage. The more the dryer is used the more often you should check the exhaust system and vent hood for proper operation.

RECOMMENDED MAXIMUM

Exhaust Hood Types

Recommended

Use only for short run installations

No. of 90º

Rigid Metal

Rigid Metal

elbows

 

 

 

 

0

90

ft.

60

ft.

1

60

ft.

45

ft.

2

45

ft.

35

ft.

3

35

ft.

25

ft.

Note: Exhausting refers to removal of moist air from the drying compartment.

8

Page 9
Image 9
Haier CGDE450AW, GDE/GDG450AW user manual Recommended Maximum