1.Fully open both shutoff valves.

2.Connect service gage manifold to the valve service ports, being sure to evacuate lines.

3.Startup the system (Refer to the Section 7 - "System Startup"). Run system at least 10 minutes to allo pressure to stabilize.

4.Temporarily install thermometer on suction (large) line near condensing unit. Be sure of good contact between thermometer and line. Wrap thermometer with insulating material to assure accurate reading.

5.Refer to Table 8 for proper system superheat. Add charge to lower superheat. Remove charge to raise superheat.

Carefully remove gage lines.

System Superheat

Ambient

 

 

Return Air Temperature ( F)

Temperature At

 

 

 

 

 

 

 

 

 

65

70

75

80

85

Condenser Inlet (

F)

 

 

 

 

 

60

 

 

17

25

30

33

37

65

 

 

13

19

26

32

35

70

 

 

5

14

20

28

32

75

 

 

5

10

17

25

29

80

 

 

 

5

12

21

26

85

 

 

 

5

10

17

20

90

 

 

 

 

7

12

18

95

 

 

 

 

5

5

5

100

 

 

 

 

 

5

5

Table 8:System charging table by superheat

6.4.ELECTRICAL WIRING

! WARNING -

A means of strain relief must be installed to this appliance at the electrical service entrance. Make sure that interconnecting wires between indoor and outdoor units meet the standards, codes and regulations. Incomplete connection or fixing of the wire could result in a fire.

A means of strain relief must be installed to this appliance at the electrical service entrance. Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet. It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.

Perform electrical work according to the installation manual and be sure to use an exclusive circuit. If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.

Ground the unit. Do not connect the ground to a gas pipe, water pipe, lighting rod or telephone ground. Defective grounding could cause an electric shock.

Electrical installation will consists of power supply wiring to the condensing unit and control wiring between thermostat, indoor unit and the condensing unit. All wiring must be in accordance with National Electrical Code and/or local ordinances that may apply.

(See unit wiring diagram furnished with this instruction).

Note: Some states need the power supply wiring within special tybe be careful to use the waterproof tube when installation the outdoor unit power supply wiring.(See the figure 4)

Figure 4-1

Figure 4-2

10

Page 12
Image 12
Haier HC18-60C1VAR, HC18-60D1VAR, HC18-60A1VAR/S operation manual Electrical Wiring, System charging table by superheat

HC18-60A1VAR/S, HC18-60D1VAR, HC18-60C1VAR specifications

Haier, a recognized brand in the home appliance sector, has consistently focused on delivering innovative and reliable products to enhance consumer convenience. Among their impressive offerings are the Haier HC18-60C1VAR, HC18-60A1VAR/S, and HC18-60D1VAR, which are compact and versatile refrigeration solutions designed to meet diverse storage needs.

The Haier HC18-60C1VAR is known for its impressive capacity and energy efficiency. With a total storage capacity that effectively accommodates a variety of food items, it is perfect for small kitchens, apartments, or dormitories. The unit features a user-friendly design that includes adjustable shelves, ensuring that users can customize the internal space according to their storage requirements. The efficient cooling technology employed in this model ensures that food remains fresh for longer periods while minimizing energy consumption.

Similarly, the HC18-60A1VAR/S model stands out with its sleek finish and modern aesthetics. This model integrates advanced cooling technology that enhances temperature stability, preventing food spoilage. The inclusion of a reversible door offers added convenience, allowing users to adapt the refrigerator to their specific kitchen layout. Additional features such as an adjustable thermostat and LED lighting make it easier for users to monitor and manage their food storage effectively.

On the other hand, the HC18-60D1VAR model is specifically designed for versatility and performance. This refrigerator model is equipped with a separate freezer compartment, providing users with the ability to store frozen foods efficiently. The frost-free technology is another highlight, as it eliminates the need for manual defrosting, a common issue with traditional refrigerators. This feature not only saves time but also ensures that the freezer maintains optimal performance.

All three models share common characteristics such as quiet operation, making them ideal for residential or office environments. They are designed with environmentally friendly refrigerants, ensuring compliance with modern sustainability standards. The easy-to-clean interiors and exterior surfaces also facilitate maintenance, adding to their user-friendly appeal.

In summary, the Haier HC18-60C1VAR, HC18-60A1VAR/S, and HC18-60D1VAR are exemplary compact refrigerators that blend performance, efficiency, and design. With features like adjustable shelving, energy efficiency, and user-friendly technologies, these models cater to the needs of modern consumers looking for reliable refrigeration solutions. Whether for small homes, offices, or student housing, Haier has a model that fits seamlessly into any lifestyle.