Table 4:System Cooling Capacity
Outdoor Unit | With This Indoor Air handler |
|
|
|
| ||
Model Number | Air Handler | Compressor | Cooling Capacity (Btu/h) | SEER | Rated | ||
|
|
|
|
|
|
| CFM(Outdoor) |
|
| brand | Sensible | Total |
| ||
HC18C1VAR | HB2400VC1M20 | Bristol | 14820 | 19000 |
| 12 | 1950 |
HC24C1VAR | HB2400VC1M20 | Bristol | 18720 | 24000 |
| 12 | 1950 |
HC30C1VAR | HB3600VA1M20 | Bristol | 23400 | 30000 |
| 12 | 1950 |
HC36C1VAR | HB3600VC1M25 | Bristol | 25920 | 36000 |
| 12 | 2700 |
HC42C1VAR | HB4800VA1M25 | Bristol | 30240 | 42000 |
| 12 | 2900 |
HC48C1VAR | HB4800VA1M25 | Bristol | 34560 | 48000 |
| 12 | 2900 |
HC60C1VAR | HB6000VC1M25 | Bristol | 41800 | 58000 |
| 12 | 2900 |
The dimensions for the condensing unit are illustrated in Figure 1. Physical and electrical specifications are provided in Table 5 for 13 SEER systems respectively.
Table 5: Model:HC18-60D1VAR
MODEL: |
| HC18D1VAR | HC24D1VAR | HC30D1VAR | HC36D1VAR | HC42D1VAR | HC48D1VAR | HC60D1VAR |
Unit Supply Voltage |
|
|
|
|
|
| ||
Normal Voltage Range |
|
|
| 197 - 253 |
|
|
| |
Compressor Brand |
|
|
| Bristol |
|
|
| |
Minimum Circuit Amps | 8.6 | 11.6 | 12.4 | 15.9 | 17.7 | 21.8 | 33.3 | |
Max Fuse or Max CKT. BKR. |
|
|
|
|
|
|
| |
(HACR per NEC ) | 15 | 20 | 20 | 25 | 30 | 35 | 55 | |
| Rated Load Amps | 6.2 | 8.6 | 9.2 | 11.7 | 13.0 | 15.8 | 25.0 |
Compressor | Locked Running |
|
|
|
|
|
|
|
| Amps | 41 | 60 | 60 | 73 | 85 | 90 | 150 |
|
|
|
|
|
|
|
|
|
| Full Load Amps | 0.86 | 0.86 | 0.86 | 1.3 | 1.43 | 2.0 | 2.0 |
|
|
|
|
|
|
|
|
|
Fan Motor | Rated HP | 1/8 | 1/6 | 1/6 | 1/4 | 1/3 | 1/3 | 1/3 |
| Nominal RPM | 1000 | 840 | 840 | 850 | 1075 | 960 | 880 |
Liquid Line OD - In (mm) | 3/8"[9.52] | 3/8"[9.52] | 3/8"[9.52] | 3/8"[9.52] | 3/8" [9.52] | 3/8"[9.52] | 3/8"[9.52] | |
|
|
|
|
|
|
|
|
|
Vapor Line OD - In (mm) | 3/4"[19.05] | 3/4"[19.05] | 3/4"[19.05] | 7/8"[22.2] | 7/8"[22.2] | 7/8"[22.2] | 7/8"[22.2] | |
|
|
|
|
|
|
|
|
|
93.64[2650] | 102.47[2900] | 121.91[3450] | 134.28[3800] | 148.41[4200] | 178.45[5050] | 196.11[5550] | ||
|
|
|
|
|
|
|
|
|
Net Dimensions - In (mm) | 23*23*31 1/2 | 30 1/4*30 1/4*27 3/4 | 30 1/4*30 1/4*31 1/2 | 30 1/4*30 1/4*31 1/2 | 30 1/4*30 1/4*35 1/2 | 30 1/4*30 1/4*31 1/2 | 30 1/4*30 1/4*35 1/2 | |
W*D*H |
| [585* 585*805] | [770* 770*705] | [770* 770*805] | [770 *770*805] | [770 *770*905] | [770 *770*805] | [ 770 *770*905] |
|
|
|
|
|
|
|
|
|
Shipping Dimensions - In (mm) | 24 3/4*24 3/4*36 | 32 3/4*32 3/4*32 1/2 | 32 3/4*32 3/4*36 | 32 3/4*32 3/4*36 | 32 3/4*32 3/4*40 1/2 | 32 3/4*32 3/4*36 | 32 3/4*32 3/4*40 1/2 | |
W*D*H |
| [632* 632*919] | [832* 832*830] | [ 832* 832*930] | [832*832*930] | [832*832*1030] | [832*832*930] | [832*832*1030] |
|
|
|
|
|
|
|
|
|
Net Weight - Lbs (kg) | 156[71] | 194[88] | 198[90] | 203[92] | 231[105] | 244[111] | 258[117] | |
|
|
|
|
|
|
|
|
|
Approx Shipping Weight - Lbs (kg) | 167[76] | 209[95] | 216[98] | 220[100] | 249 [113] | 262[119] | 282[128] | |
|
|
|
|
|
|
|
|
|
Table 6:System Cooling Capacity
Outdoor Unit | With This Indoor Air handler |
|
|
|
| ||
Model Number | Air Handler | Compressor | Cooling Capacity (Btu/h) | SEER | Rated | ||
|
| brand | Sensible | Total |
|
| CFM(Outdoor) |
HC18D1VAR | HB2400VD1M20 | Bristol | 13300 | 18000 |
| 13 | 1350.0 |
HC24D1VAR | HB2400VD1M20 | Bristol | 17700 | 24000 |
| 13 | 1800.0 |
HC30D1VAR | HB3600VD1M22 | Bristol | 20669 | 28000 |
| 13 | 2100 |
HC36D1VAR | HB3600VD1M22 | Bristol | 25900 | 35000 |
| 13 | 2700 |
HC42D1VAR | HB4800VD1M22 | Bristol | 29600 | 40000 |
| 13 | 3200 |
HC48D1VAR | HB4800VD1M22 | Bristol | 34800 | 47000 |
| 13 | 3600 |
HC60D1VAR | HB6000VD1M22 | Bristol | 40700 | 55000 |
| 13 | 4000 |
4