Haier HDU-42CF03/H installation manual Installation Manual For Electric Wiring, Electric wiring

Models: HDU-42CF03/H

1 34
Download 34 pages 5.12 Kb
Page 33
Image 33
 Installation Manual For Electric Wiring

5. Electric wiring Installation Manual For Electric Wiring

5. Electric wiring

Manual backgroundManual background WARNING

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1)Selection of size of power supply and interconnecting wires. Precautions for Electric wiring

Manual background Electric wiring work should be conducted only by authorized personnel.

Manual background Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.

Manual background Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)

Item

 

Circuit

breaker

Power source

Earth leakage breaker

 

 

 

 

 

Model

Phase

Switch breaker

Overcurrent protector

wire size

Switch

Leak

 

(A)

rated capacity (A)

(minimum)

breaker

current

HDU-42CF03/H

3

30

20

2.5mm2

30

30mA

HDU-42HF03/H

 

 

 

 

 

 

(2)Wiring connection

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.

Note: remember to connect the black terminal of indoor unit with the black terminal of outdoor unit properly using the connecting wire in the accesory bag,and connect the blue terminal of indoor unit with the white terminal of out terminal as the same(For heat pump model).For cooling only unit,just connect the black terminalof indoor unit with the black terminal of outdoor unit properly.Otherwise the wired controller will display "E4" or "E6" malfunction refer to Page.16.

HDU-42CF03/H

OUTDOOR UNIT TERMINAL BLOCK

HDU-42HF03/H

Y/G OUTDOOR UNIT TERMINAL BLOCK Y/G

Manual backgroundManual background Y/G R S T N 1 2 3 Manual background

POWER SUPPLY: 3N~,380-400V , 50Hz

1

2

3

4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R S T N

POWER SUPPLY: 3N~,380-400V,50Hz

L N 3 4 5

1 2 3 4 5

INDOOR UNIT TERMINAL BLOCK

INDOOR UNIT TERMINAL BLOCK

32

Page 33
Image 33