Haier HSU-12HG13-B, HSU-09HG13-B, 0010518181 Outdoor unit, Purging Method, 9k 12k

Models: 0010518181 HSU-12HG13-B HSU-09HG13-B

1 8
Download 8 pages 15.66 Kb
Page 7
Image 7
5.Purging Method:

Outdoor unit

5.Purging Method:

Push the air out of the indoor unit and piping as followes:

(1)Remove the valve cap on 2-way valve in outdoor unit.

(2)Loosen by 1/2 turn the flare nut of gas pipe, which is conneted to 3-way valve.

(3)Loosen 2-way valve by 90o using hexagon wrench, and after approx. 10 sec tighten it up. Gas comes out through flare nut on wide pipe. If no gas is discharged, tighten flare nut with specified torque.

(4)Open 2-way and 3-way valves using specified torque.

(5)Tighten the caps on the valves with specified torque.

 

Tighten torque N.m

 

 

Valve rod

7-9

 

 

Valve cap

20-25

 

 

2-way valve 9k 12k 6.35mm(1/4")

3-way valve Manual background9.52mm(3/8")

Manual background12.7mm(1/2")

HSU-09HG13-B

HSU-12HG13-B

Manual background When connecting pipe exceeds 5 meters, 20g refrigerant

shall be added per exceeding meter . Charge according to the following list.

 

for

9k 12k

 

Piping length

5m

7m

10m

 

 

 

 

Additional amount

No need

40g

100g

 

 

 

 

Manual background Note: When extending piping, air inside piping shall be removed by using external refrigerant gas, charge according to the following list.

Brand new outdoor unit is charged 50g more refrigerant than regulated weight. Only for first installation, this extra 50g can be used to purge air in pipes.

Manual background During this procedure, 50g refrigerant will be discharged in piping. (This must be strictly controlled within 90o and 10 sec.)

7

Page 7
Image 7
Haier HSU-12HG13-B, HSU-09HG13-B, 0010518181 installation manual Outdoor unit, Purging Method, 9k 12k