Outdoor unit

5.Installation instruction on the outdoor part of the fresh air device

1.Remove the four screws of fresh air box from the back cover.

2.Use six screws to fix fresh air box onto the designated position on the outdoor unit. 3.Remove two screws of the pipe junction of the fresh air box, then insert the flared departure of

the change for fresh air tube into the pipe junction and then fix with the screws. 4.Use four screws to fix the fresh air box onto the back cover, as illustrated:

 

 

Screw

Back

 

Fresh air tube

 

 

hole

cover

 

 

 

 

Flared departure

Change-for-fresh-air box

 

 

 

 

Fresh air box

Dust

 

 

 

 

Fresh air

 

 

 

Fresh air tube

Screw

Screw

Connecting terminal

 

filtration

box

 

mesh

 

 

Joint of tube

Fresh air signal

Fresh air tube

wire

 

(with guard ring)

 

Note:After wiring, the connecting terminals of outdoor unit and change-fresh-air as well as the wiring sheath should be placed in the change-for-fresh-air box against the rain.

6.Purging Method:

Push the air out of the indoor unit

 

 

 

 

 

2-way valve

3-way valve

and piping as followes:

 

 

 

 

 

2-way valve

 

 

 

 

 

6.35mm(1/4")

12.7mm(1/2")

(1) Remove the valve cap on 2-way valve in outdoor unit.

 

6.35mm(1/4")

 

 

 

(2) Loosen by 1/2 turn the flare nut of gas pipe, which is

 

3-way valve

 

 

is conneted to 3-way valve.

 

 

 

 

 

 

 

 

9.52mm(3/8")

 

 

(3) Loosen 2-way valve by 90o using hexagon wrench,

 

 

 

and after approx.10 sec tighten it up. Gas comes out

 

12.7mm(1/2")

 

 

 

 

 

 

 

through flare nut on wide pipe. If no gas is discharged,

 

 

 

 

 

tighten flare nut with specified torque.

 

 

HSU-09C03/VA(ZXF)

HSU-18C03/V(ZXF)

(4) Open 2-way and 3-way valves using specified torque.

 

HSU-09H03/VA(ZXF)

HSU-18H03/V(ZXF)

(5) Tighten the caps on the valves with specified torque.

 

HSU-12C03/VA(ZXF)

HSU-12H03/VB(ZXF)

 

Tighten torque N.m

 

 

 

HSU-12H03/VA(ZXF)

HSU-12H03/V(ZXF)

 

 

 

 

2-way valve

3-way valve

 

Valve rod

 

7-9

 

 

 

 

 

 

 

 

 

 

9.52mm(3/8")

15.88mm(5/8")

 

Valve cap

 

20-25

 

 

 

 

 

 

 

 

 

 

 

 

HSU-24C03/V(ZXF)

When connecting pipe exceeds 5 meters, 20g or 60g

 

 

 

 

 

 

HSU-24C03/V(ZF)

 

(only for 22k24k) refrigerant shall be added per exceeding

 

 

HSU-24H03/V(ZXF)

meter. Charge according to the following list.

 

 

 

HSU-24H03/V(ZF)

 

 

for 9k 12k 18k

for

22k 24k

 

 

 

HSU-24HK0307

 

 

 

 

 

HSU-24HD0307

 

Piping length

 

7m 10m

5m

7m 10m

 

 

 

 

5m

20m

 

 

HSU-22C03/V(ZXF)

Additional amount No need 40g 100g No need 120g 300g

900g

 

 

HSU-22H03/V(ZXF)

 

 

HSU-22C03/V(ZF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HSU-22H03/V(ZF)

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

 

 

A

 

A

Outdoor unit

 

A

 

 

 

 

 

 

 

 

 

Outdoor unit

 

B

 

B

 

 

Oil trap

 

 

Indoor unit

 

 

 

C

 

 

 

 

 

 

 

 

 

 

B

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

Max.Elevation:

for 9K 12K: B=5m

 

 

 

 

 

 

 

 

 

for 18K 22K 24K: B=10m

 

CAUTION

 

 

 

Max. Length:

for 9K :

A=7m

 

 

oil trap C

 

 

In case more than 5 metres

 

 

 

 

for 12K:

A=10m

 

should be installed every 5~7m.

 

 

 

 

for 18K 22K 24K: A=20m

 

 

 

 

 

12.7mm(1/2") Note: When extending piping, air inside piping shall be removed by using external refrigerant gas,

charge according to the following list.

Brand new outdoor unit is charged 50g or 80g(22k,24k) more refrigerant than regulated weight. Only for first installation, this extra 50g or 80g(22k,24k) can be used to purge airin pipes.