Outdoor unit
5.Installation instruction on the outdoor part of the fresh air device
1.Remove the four screws of fresh air box from the back cover.
2.Use six screws to fix fresh air box onto the designated position on the outdoor unit. 3.Remove two screws of the pipe junction of the fresh air box, then insert the flared departure of
the change for fresh air tube into the pipe junction and then fix with the screws. 4.Use four screws to fix the fresh air box onto the back cover, as illustrated:
|
| Screw | Back |
| Fresh air tube |
|
| hole | cover |
| |
|
|
| Flared departure | ||
|
|
|
| ||
Fresh air box | Dust |
|
|
| |
| Fresh air |
|
| ||
| Fresh air tube | Screw | Screw | ||
Connecting terminal |
| filtration | box | ||
| mesh |
|
| Joint of tube |
Fresh air signal | Fresh air tube |
wire |
|
(with guard ring) |
|
Note:After wiring, the connecting terminals of outdoor unit and
6.Purging Method:
Push the air out of the indoor unit |
|
|
|
|
| |||||
and piping as followes: |
|
|
|
|
| |||||
|
|
|
|
| 6.35mm(1/4") | 12.7mm(1/2") | ||||
(1) Remove the valve cap on |
| 6.35mm(1/4") | ||||||||
|
|
| ||||||||
(2) Loosen by 1/2 turn the flare nut of gas pipe, which is |
|
|
| |||||||
is conneted to |
|
|
|
|
| |||||
|
|
| 9.52mm(3/8") |
|
| |||||
(3) Loosen |
|
|
| |||||||
and after approx.10 sec tighten it up. Gas comes out |
| 12.7mm(1/2") |
|
| ||||||
|
|
|
|
| ||||||
through flare nut on wide pipe. If no gas is discharged, |
|
|
|
|
| |||||
tighten flare nut with specified torque. |
|
| ||||||||
(4) Open |
| |||||||||
(5) Tighten the caps on the valves with specified torque. |
| |||||||||
| Tighten torque N.m |
|
|
|
| |||||
|
|
|
|
| ||||||
Valve rod |
|
|
|
|
|
| ||||
|
|
|
|
| 9.52mm(3/8") | 15.88mm(5/8") |
| |||
Valve cap |
|
|
|
|
|
| ||||
|
|
|
|
|
|
| ||||
When connecting pipe exceeds 5 meters, 20g or 60g |
|
|
| |||||||
|
|
|
| |||||||
(only for 22k24k) refrigerant shall be added per exceeding |
|
| ||||||||
meter. Charge according to the following list. |
|
|
|
| ||||||
| for 9k 12k 18k | for | 22k 24k |
|
|
|
|
| ||
|
|
|
|
| ||||||
Piping length |
| 7m 10m | 5m | 7m 10m |
|
|
|
| ||
5m | 20m |
|
| |||||||
Additional amount No need 40g 100g No need 120g 300g | 900g |
|
| |||||||
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| Indoor unit |
|
|
| Outdoor unit |
|
|
| |
|
| A |
| A | Outdoor unit |
| A |
|
| |
|
|
|
|
|
|
| ||||
Outdoor unit |
| B |
| B |
|
| Oil trap |
| ||
| Indoor unit |
|
|
| C |
|
| |||
|
|
|
|
|
|
|
| B | Indoor unit |
|
|
|
|
|
|
|
|
|
|
| |
Max.Elevation: | for 9K 12K: B=5m |
|
|
|
|
|
| |||
|
|
| for 18K 22K 24K: B=10m |
| CAUTION |
|
|
| ||
Max. Length: | for 9K : | A=7m |
|
| oil trap C |
| ||||
| In case more than 5 metres |
| ||||||||
|
|
| for 12K: | A=10m |
| should be installed every 5~7m. |
| |||
|
|
| for 18K 22K 24K: A=20m |
|
|
|
|
|
Note: When extending piping, air inside piping shall be removed by using external refrigerant gas,
charge according to the following list.
Brand new outdoor unit is charged 50g or 80g(22k,24k) more refrigerant than regulated weight. Only for first installation, this extra 50g or 80g(22k,24k) can be used to purge airin pipes.
During this procedure, 50g or 80g(22k,24k) refrigerant will be discharged in piping.(This must be strictly controlled within 90o and 10 sec.)
7