INSTALLATION
1)Check all clearances to combustibles, page 6.
2)Make the gas connection. See page 7.
3)Install the 3" flue liner to the sliding connec- tor plate. See page 7.
4)Slide the unit half way into the fireplace.
5)Pull the vent connector plate through the tapered brackets and fasten to the front plate. See page 7.
6)Slide the unit fully into the fireplace.
7)Test gas pressure, page 8. Check aeration system, page 8.
8)Install the optional brick panels. See page 8.
9)Install the log set. See page 9.
10)Assemble and install the faceplate and trim. See page 10.
MATERIALS REQUIRED
No electrical power supply is required for the gas control to operate. A 120 Volt AC power cord is hooked up to the fan. Plug the 3 wire cord into a suitable receptacle. Do not cut the ground terminal off under any circum- stances. When connected with 120 volts, the appliance must be electrically grounded in ac- cordance with local codes, current version of CSA C22.1 (in Canada) or in the absence of local codes, with the National Electrical Code ANSI/NFPA
NOTE: This unit is equipped with a heat sensor thermodisc which will prevent the blower from operat- ing until the unit reaches the cor- rect temperature.
MINIMUM FIREPLACE
DIMENSIONS
CLEARANCES TO COMBUSTIBLES
Minimum Clearances to Combustibles
From Unit |
| |
Sides | A | 10" / 255 mm |
Ceiling | B | 47.5" / 1205 mm |
Mantel | C | see Dia. 2 & 3 |
From Standard Surround (26" x 40") | ||
Sides | D | 4" / 100 mm |
Ceiling | E | 41.5" / 1055 mm |
Mantel |
| see Dia. 2 & 3 |
Max. Mantle Depth | G | 12" / 305 mm |
|
| (see Dia. 2) |
Hearth Height | H | 0" / 0 mm |
Hearth Depth | I | 16" / 405 mm |
Hearth Width | J | 40" / 1015 mm |
Min. Alcove Width | K | 48" / 1220 mm |
Max. Alcove Depth | L | 36" / 915 mm |
11)Install the glass front (flush or bay). See pages 10 and 11.
12)Install optional glass trim, or door fire screens. See pages 11 and 12.
13)Install both louvers (flush or bay). See pages 11 and 12.
14)Install optional remote control or wall ther- mostat, pages 15.
15)Final check: Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly. This in- cludes:
a)Clocking the appliance to ensure the correct firing rate.
b)Adjusting the primary air, if required, to ensure that the flame does not carbon. See page 8.
c)Ensuring that the appliance is venting correctly.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1)Ensure that structural members are not cut or weakened during installation.
2)Ensure proper grounding using the #8 ground lug provided.
3)Appliance must be anchored to the floor with the supplied anchoring methods.
The minimum fireplace clearances & dimen- sions for the FPI gas insert are shown in the following diagrams:
Diagram 1
Combustible Mantel Clearances
with Bay & Flush Louvers in
Masonry and Factory Built
Fireplace Installation
*Note: If you are installing the Molded Faceplate, the minimum fireplace dimen- sions are as follows:
Width (at front): 29" | (737mm) | |
Depth: | 15" | (381mm) |
Diagram 2
6 |