Harman Stove Company 1-90-79700 owner manual Flue Liner with Required Air Space, Smoke Chamber

Models: 1-90-79700

1 40
Download 40 pages 30.85 Kb
Page 18
Image 18
Minimum 8" Masonry

Oakleaf Woodburning Stove

Oakleaf to Flue Fireplace Conversion (Minimum NFPA 211 Liner Connection)

Flue Liner with Required

Air Space

Stainless Steel Chimney Connector Must Extend to Flue Liner

Minimum 8" Masonry

Thickness in Front of

Smoke Chamber

Use Damper Adapter or Seal with Non- Combustible Material

Damper Plate is Removed or Fastened in Open Position

Listed Fireplace

Trim Protection for

Reduced Clearance

Floor Protection*

Combustible Floor

Airtight insulated Clean-Out

*Floor Protection in Accordance with Solid Fuel Appliance Listing

NOTICE: When using rear flue configuration, a new upper rear heat shield, #1-00-797066 must be installed in place of the existing shield.

The Chimney Connector Shall Not Pass Through an Attic or Roof Space, Closet or Similar Concealed Space, a Floor or Ceiling.

18 Dry Seasoned Wood Only!

3-90-798

Save These Instructions

Page 18
Image 18
Harman Stove Company 1-90-79700 Flue Liner with Required Air Space, Minimum 8 Masonry Thickness in Front of, Smoke Chamber