Hatco IMPERIAL "S manual Specifications

Models: IMPERIAL "S

1 40
Download 40 pages 7.91 Kb
Page 7
Image 7
SPECIFICATIONS

SPECIFICATIONS

CIRCUIT BREAKER & FUSED DISCONNECT SWITCH SIZES - 4 TO 12 kW

kW

Volts*

Phase

 

Amp Draw

 

 

Breaker or

Copper

Conduit

 

 

 

L1

 

L2

 

L3

 

Fuse Size

Wire Size

Size

 

 

 

 

 

 

 

 

 

 

 

 

4

208

1

19

 

19

 

-

30

10

1/2" (13 mm)

 

240

1

17

 

17

 

-

30

10

1/2" (13 mm)

 

480

1

8

 

8

 

-

15

14

1/2" (13 mm)

5

208

1

24

 

24

 

-

30

10

1/2" (13 mm)

 

240

1

21

 

21

 

-

30

10

1/2" (13 mm)

 

480

1

10

 

10

 

-

15

14

1/2" (13 mm)

6

208

1

29

 

29

 

-

40

8

1/2" (13 mm)

 

208

3

14

 

25

 

14

40

8

1/2" (13 mm)

 

240

1

25

 

25

 

-

40

8

1/2" (13 mm)

 

240

3

13

 

22

 

13

30

10

1/2" (13 mm)

 

380

3

9.2

 

9.2

 

9.2

15

14

1/2" (13 mm)

 

480

3

6

 

11

 

6

15

14

1/2" (13 mm)

 

600

3

5.7

 

5.7

 

5.7

15

14

1/2" (13 mm)

7

208

1

34

 

34

 

-

50

8

1/2" (13 mm)

 

208

3

17

 

29

 

17

40

8

3/4" (19 mm)

 

240

1

29

 

29

 

-

40

8

1/2" (13 mm)

 

240

3

15

 

25

 

15

40

8

1/2" (13 mm)

 

380

3

11.4

 

11.4

 

11.4

15

14

1/2" (13 mm)

 

480

3

7

 

13

 

7

20

12

1/2" (13 mm)

 

600

3

6.7

 

6.7

 

6.7

15

14

1/2" (13 mm)

9

208

1

43

 

43

 

-

60

6

1/2" (13 mm)

 

208

3

22

 

38

 

22

50

8

1/2" (13 mm)

 

240

1

38

 

38

 

-

50

8

1/2" (13 mm)

 

240

3

19

 

33

 

19

50

8

1/2" (13 mm)

 

380

3

13.3

 

13.3

 

13.3

20

12

1/2" (13 mm)

 

480

3

9

 

16

 

9

20

12

1/2" (13 mm)

 

600

3

8.7

 

8.7

 

8.7

15

14

1/2" (13 mm)

9.9

208

1

47.5

 

47.5

 

-

60

6

1/2" (13 mm)

 

208

3

27.5

 

27.5

 

27.5

40

8

1/2" (13 mm)

10.4

208

3

28.8

 

28.8

 

28.8

40

8

1/2" (13 mm)

10.5

208

1

51

 

51

 

-

70

4

3/4" (19 mm)

 

208

3

29

 

29

 

29

40

8

1/2" (13 mm)

 

240

1

44

 

44

 

-

60

6

1/2" (13 mm)

 

240

3

25.3

 

25.3

 

25.3

40

8

1/2" (13 mm)

 

480

3

12.6

 

12.6

 

12.6

20

12

1/2" (13 mm)

 

600

3

10

 

10

 

10

15

14

1/2" (13 mm)

11.4

240

1

47.5

 

47.5

 

-

60

6

1/2" (13 mm)

 

240

3

27.5

 

27.5

 

27.5

40

8

1/2" (13 mm)

 

480

3

13.7

 

13.7

 

13.7

20

12

1/2" (13 mm)

12

208

1

58

 

58

 

-

90

3

1" (25 mm)

 

208

3

33

 

33

 

33

50

8

1/2" (13 mm)

 

240

1

50

 

50

 

-

70

6

1/2" (13 mm)

 

240

3

29

 

29

 

29

40

8

1/2" (13 mm)

 

380

3

19.1

 

19.1

 

19.1

30

10

1/2" (13 mm)

 

480

3

14.5

 

14.5

 

14.5

20

12

1/2" (13 mm)

 

600

3

11.6

 

11.6

 

11.6

15

14

1/2" (13 mm)

 

 

 

 

 

 

 

 

 

 

 

 

Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based on conductors plus ground wire sizing per Table C1 from Appendix C.

Only 6, 7 & 9 kW models can be field converted to single or three phase (open delta on 3 phase). Larger branch circuit required than for balanced 3 phase of equal kW. Balanced 3 phase available, consult factory.

NOTE: 250 kcmil maximum wire size for terminal block.

5

Form No. EBOOSTERM-0406

Page 7
Image 7
Hatco IMPERIAL "S manual Specifications