Page 7
Isle Royale Wood Stove
R
September 1, 2008 250-5763C
FLOOR PROTECTION
The oor must be non-combustible material, extending beneath heater and to the front, sides and rear as indicated. The
oor must be non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks
and falling embers. A layer of thin brick or ceramic tile over a combustible oor is not sufcient. See Alternate oor protec-
tion calculation sample on page 8.
In USA installations, it is necessary to install a oor protector 16 inches in front and 8 inches to both sides of the loading
door. See *exception below.
In Canada, similar oor protection must be provided 18 inches (457mm) in front and 8 inches (203mm) from the sides and
rear of the stove. See *exception below.
*ExCEPTION: Non combustile oor protections must extend beneath the ue pipe when installed with horizontal venting
and extend 2 inches (51mm) beyond each side.
CANADA
203mm (8")
203mm
(8")
203mm
(8")
457mm (18")
1251mm
(49-1/4")
Minimum
1137mm (44-3/4")
Minimum
16" from glass - std legs 8"

USA

Fuel loading door
36-3/4"
Minimum
39-1/4"
Minimum
must extend
length of flue and
2" (51mm)
beyond each
side of pipe
USA - Required
CANADA - Recommended
16"
optional coverage
optional
coverage
optional
coverage
8”
36-9/16"
required coverage
38-5/8"
51"
30-3/8"
51"
USA Installations
fuel loading door