C. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.

Combustible and non-combustible mantel legs, surrounds and stub walls may be constructed within the gridded area, Figure 6.3.

FLUSH

BRICK

4 in.

[102 mm]

FRONT

FRONT

11 1/4 in.

[286 mm]

 

angle

A

50°

 

 

 

 

 

B

12 in.

[305 mm]

39°

9 3/4 in.

[248 mm]

angle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

12 in.

 

 

Fireplace

Outside

[305 mm]

Model #

Opening

Dimensions

EL36

in.

36

41

 

 

 

 

 

 

 

 

mm

914

1041

 

 

 

 

 

 

 

 

 

EL42

in.

42

47

 

 

 

 

mm

1067

1194

 

 

 

 

 

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.

Framing across the top of fireplace must be above top standoffs.

2 in. (51 mm) min. air space clearance

from chimney.

C

D

Header MUST NOT be notched!

D = extra space needed for outside air connection.

If outside air duct has no bend, this dimension may be reduced as long as minimum clearances are met.

B

A

 

 

 

 

 

 

Model

 

A

B*

C**

D

 

 

 

EL36

in.

42

21 1/2

39 3/4

8

 

mm

1067

546

1010

203

 

 

 

EL42

in.

48

21 1/2

39 3/4

8

 

mm

1219

546

1010

203

 

 

* If interior of chase will be drywalled, add the thickness to

 

this measurement.

Figure 6.4 Framing the Fireplace

** Adjust header height for a raised floor under fireplace.

 

20