C. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.

Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed within the gridded area, Figure 6.3.

Grid represents 1 in. (25 mm) squares

12in.

[305 mm]

FLUSH

FRONT

50°

angle

 

36in.

[914 mm]

40in.

[1016 mm]

BRICK

FRONT

39°

angle

 

4in.

[102 mm]

9 3/4 in.

[248 mm]

12 in.

12 in.

[305 mm]

[305 mm]

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.

Framing across the top of fireplace must be above top standoffs.

You must maintain

2 in. (51 mm) min. air space clearance from the chimney to the enclosure.

Note: Fireplace Header cannot be positioned until after the fireplace assembly is in place.

41 in.

(1041 mm)

23 in.

(584 mm)

Figure 6.4 Framing the Fireplace