F. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.

Combustible or non-combustible mantel legs, surrounds and stub walls may be constructed per Figure 11.5.

squares

4 in. [102 mm]

BRICK

FRONT

Grid represents 1 in. (25 mm)

FLUSH

FRONT

9 3/4 in. [248 mm]

39°

angle

 

36 in. [914 mm]

40 in. [1016 mm]

angle

50°

 

12 in. [305 mm]

12 in. [305 mm]

12 in. [305 mm]

Figure 11.5 Mantel Leg or Wall Projections (acceptable on both sides of opening)

Heat & Glo • HST-42D • 27177 • Rev AB • 11/08

41

Page 41