Heat & Glo LifeStyle 6000TV-OAK The Gas Control Systems, C. Bedroom Installation in Canada

Models: 6000TV-OAK 6000TV-OAK-IPI

1 20
Download 20 pages 61.01 Kb
Page 14
Image 14
C. Bedroom Installation in Canada

C. Bedroom Installation in Canada

This model MUST NOT be vented into a vent system in- stalled exterior to a building. The part of the vent system above the roof line can be exterior to the building.

D.Vent Termination

!WARNING: MAJOR U.S. BUILDING CODES SPECIFY MINIMUM CHIMNEY AND/OR VENT HEIGHT ABOVE THE ROOF TOP. THESE MIN- IMUM HEIGHTS ARE NECESSARY IN THE IN- TEREST OF SAFETY. FIGURE 6 AND TABLE SHOW MINIMUM HEIGHTS, PROVIDED THE TERMINATION CAP IS AT LEAST 8-FEET FROM A VERTICAL WALL.

LOWEST

DISCHARGE

OPENING

TERMINATION

CAP

X

12

D.Vent Termination ROOF PITCH

IS X/ 12

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

ROOF PITCH

H (MIN.) FT.

FLAT TO 6/12

1.0

OVER 6/12 TO 7/12

1.25

OVER 7/12 TO 8/12

1.5

OVER 8/12 TO 9/12

2.0

OVER 9/12 TO 10/12

2.5

OVER 10/12 TO 11/12

3.25

OVER 11/12 TO 12/12

4.0

OVER 12/12 TO 14/12

5.0

OVER 14/12 TO 16/12

6.0

OVER 16/12 TO 18/12

7.0

OVER 18/12 TO 20/12

7.5

OVER 20/12 TO 21/12

8.0

Figure 6. Vent Termination

Step 5. Positioning, Leveling, and Securing the Fireplace

To properly position, level, and secure the fireplace:

Place the fireplace into position (see Figure 7).

Level the fireplace from side to side and from front to back.

Shim the fireplace with non-combustible material, such as sheet metal, as necessary.

Secure the fireplace to the framing by nailing or screwing.

Figure 7. Proper Positioning, Leveling,

and Securing of a Fireplace

Step 6. The Gas Control Systems

!WARNING: THIS UNIT IS NOT FOR USE WITH SOLID FUEL.

Two types of gas control systems are used with these models: Standing Pilot Ignition and Intermittent Pilot Ignition (IPI).

Standing Pilot Ignition System

This system includes millivolt control valve, standing pilot, thermopile/thermocouple flame sensor, and piezo ignitor.

!WARNING: 110-120 VAC MUST NEVER BE CONNECTED TO A CONTROL VALVE IN A MILLIVOLT SYSTEM.

Intermittent Pilot Ignition (IPI) System

The IPI system includes a 3V control valve, electronic mod- ule, and intermittent pilot.

!WARNING: CONTINUOUS 110-120 VAC SER-

VICE MUST BE WIRED TO THE FIREPLACE JUNCTION BOX.

14

Heat & Glo • 6000TV-OAK, 6000TV-OAK-IPI384-900 Rev. N • 11/05

Page 14
Image 14
Heat & Glo LifeStyle 6000TV-OAK The Gas Control Systems, C. Bedroom Installation in Canada, D.Vent Termination, Roof Pitch