Heat & Glo LifeStyle CFL-30LP-B, CFL-24LP-B, CFL-18LP-B, ST-CFL-24LP manual

Models: CFL-24LP-B CFL-30LP-B CFL-18LP-B ST-CFL-24LP

1 21
Download 21 pages 42.44 Kb
Page 16
Image 16
Figure 5

B.Minimum inlet gas supply pressure for purposes of input adjustment, shall be 7.0 inches w.c. (1.75kPa) for natural gas and 11.0 inches w.c. (2.75kPa) for pro- pane (LP gas). Maximum inlet gas supply pressure shall be 14.0 in. w.c. (3.5kPa) for both natural gas and propane (LP gas). Manifold (outlet) pressure should be 3.5 inches w.c. (.87kPa) for natural gas and 10.0 inches w.c. (2.5kPa) for LP gas.

C.The appliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pres- sures in excess of 1/2 psig (3.5kPa).

D.This appliance must be isolated from the gas sup- ply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).

E. NOTE: THE GAS SUPPLY LINE SHOULD BE

PURGED OF ANY TRAPPED AIR PRIOR TO THE FIRST FIRING OF THE UNIT.

F.CAUTION: During the initial purging and sub- sequent lightings, NEVER allow the gas control valve knob to remain depressed in the "PILOT" po- sition without pushing the red ignitor button at least once every second.

G.A damper stop clamp with set screw is provided to prevent full closure of the fireplace damper blade. At- tach the clamp to the edge of the damper blade with pliers or wrenches. If the damper stop supplied does not fit the application, use a permanent means that will keep the damper open to a MINIMUM of 51 square inches (328cm2). See Figure 5.

WARNING: OPEN THE CHIMNEY DAMPER TO ITS FULLY OPEN POSITION WHEN BURNING THIS GAS LOG SET.

WARNING: LOGS MUST NEVER BE BURNED WITH- OUT THE FLUE DAMPER IN THE FULL OPEN POSI- TION. FAILURE TO DO SO IS DANGEROUS TO YOUR HEALTH AND VOIDS ALL WARRANTIES.

H. NOTE: The Commonwealthof Massachusetts re- quires that the chimney flue damper, when used with gas logs, shall be welded open or completely removed.

I. Your appliance control system is a millivolt type. It consists of a pilot burner, a gas control valve/regulator, a thermopile, a piezo ignitor, and an ON/OFF rocker switch. See Figure 6 for control system wiring diagram.

J. NOTE: An Optional Remote Control Kit and Wall Switch Kit , for turning the burner ON/OFF are avail- able. Detailed installation instructions are found in each kit.

K. Test fire the unit after referring to the SAFETY IN- FORMATION and LIGHTING INSTRUCTIONS found in Section 3 in this manual, or on the label plate as- sembly found on the gas-burner.

L. After the gas line installation is complete, all con- nections must be tightened and checked for leaks with

acommercially-available, non-corrosive leak check solution. Be sure to rinse off all leak check solution following testing. Refer to Section 3, OPERATING GUIDELINES and MAINTENANCE INSTRUCTIONS.

M. Once the gas-burner is test fired and gas supply lines are purged, assemble the grate(s) and logs. Be certain to follow the Log Placement Instructions shipped with your unit. Remember to keep the Log Instructions along with this manual for future use.

Figure 5

Figure 6

16

Heat & Glo • CFL-18/24/30-B, ST-CFL-24526-900 Rev. F • 7/05

Page 16
Image 16
Heat & Glo LifeStyle CFL-30LP-B, CFL-24LP-B, CFL-18LP-B, ST-CFL-24LP manual