Step 5. Gas Pressure Requirements
Pressure requirements for these gas appliances are shown in the table below.
Pressure | Natural Gas | Propane |
Minimum | 5.0 inches | 11.0 inches |
Inlet Pressure | w.c. | w.c. |
Maximum Inlet | 14.0 inches | 14.0 inches |
Gas Pressure | w.c. | w.c. |
Manifold | 3.5 inches | 10.0 inches |
Pressure | w.c. | w.c. |
Inlet and outlet pressure taps are provided on the front face of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.
THE FIREPLACE AND ITS INDIVIDUAL
Step 6. Wiring the Fireplace
NOTE: Electrical wiring must be installed by a li- censed electrician.
CAUTION: DISCONNECT REMOTE CONTROLS IF AB- SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE- VENT ACCIDENTAL APPLIANCE OPERATION.
For Standing Pilot Ignition Wiring
Appliance Requirements
•This appliance DOES NOT require
•Models
!WARNING: DO NOT CONNECT
Wall Switch
Position the wall switch in the desired position on a wall. Run a maximum of 25 feet (7.8 m) or less length of 18 A.W.G. minimum wire and connect it to the fireplace valve pigtails.
!WARNING: DO NOT CONNECT
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC- TION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
THERMOCOUPLE
GAS
VALVE
THERMOPILE |
|
| ON |
| OFF |
| ROCKER |
RED T1 | SWITCH |
WHITE T2 |
|
OPTIONAL WALL SWITCH
THERMOSTAT OR REMOTE
Figure 8. Standing Pilot Ignition Wiring Diagram
19