B. Clearances

Warning! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig- ure 6.2. Do NOT pack required air spaces with insulation or other materials.

Storm Collar

Roof Flashing

(attic)

(insulation)

Shaded areas

represent

2 in. (51 mm) min.

air space clearance required around pipe

Attic

Insulation

Shield

(ceiling)

2 in. (51 mm) min.

Offset/Return (secured

with hanger straps)

(ceiling)

Ceiling Firestop

Object

48 in.

 

Combustible

1219 mm

0 in.

 

 

to floor

Must have 2 in. (51 mm)

minimum clearance

to header

0 in. to level of standoffs

1/2 in. (13 mm) to back & sides of appliance

Figure 6.2 Clearances to Combustible Materials

Note: Chimney air kit is not shown, but is required in Canada.