Heat & Glo LifeStyle PIER-40 owner manual A. Chimney Requirements

Models: PIER-40

1 52
Download 52 pages 27.91 Kb
Page 25
Image 25
A. Chimney Requirements

A. Chimney Requirements

Measure vertical distances from the base of the fireplace as shown in Figure 8.2.

Minimum overall straight height

14

(4.27 m)

Minimum height with offset/return

16.5 ft

(5.03 m)

• Maximum height

90 ft

(27.43 m)

• Maximum chimney length between an offset

20 ft

(6.1 m)

 

and return

 

 

• Maximum distance between chimney

35 ft

(10.67 m)

 

stabilizers

 

 

Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length

6 ft

(1.83 m)

 

between the offset and return

 

 

• Maximum unsupported chimney height above

35 ft

(10.67 m)

 

the fireplace

 

 

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

Warning! Risk of Fire! You must maintain 2 in. (51

mm)air space clearance to insulation and other combus- tible materials around the chimney system. Failure to do so may cause overheating and fire.

Table 8.1

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

 

 

 

SL11

4-3/4

121

 

 

 

 

Ceiling Firestops

 

 

 

FS538

0

0

 

 

 

 

 

FS540

0

0

Offsets/Returns

 

 

 

SL1130

18

457

 

 

 

 

Roof Flashing

 

 

 

RF570

0

0

 

 

 

 

 

RF571

0

0

Determine the chimney components needed to complete your particular installation:

Measure the total vertical height of the fireplace installation from the base of the fireplace assembly to the approximate location of the bottom of the termination cap.

Subtract the effective height of the fireplace assembly (see Figure 8.2) from the total vertical height to determine the overall height of the chimney installation.

Create a schematic for your application similar to Figure 8.2 showing components required (referring to Table 8.1). Figure 8.1 identifies those components and where used.

Install a ceiling firestop whenever the chimney penetrates a floor/ceiling.

Notice: A maximum of two pairs of offsets and returns may be used.

Caution! Risk of Fire and/or Asphyxiation! DO NOT connect this fireplace to a chimney flue servicing another appliance. Do NOT connect to any air distribu- tion duct or system. These actions could cause over- heating/fire in the chimney flue, or release of exhaust fumes into the living areas.

6 ft (1.83 m) max. unsupported chimney above roof

20 ft (6.10 m) max. pipe between an offset & return Table 8.1

Chimney Sections*

 

 

 

SL1106

4-3/4

121

 

 

 

 

 

SL1112

10-3/4

273

 

SL1118

16-3/4

425

 

SL1136

34-3/4

883

 

 

 

 

 

SL1148

46-3/4

1187

* Dimensions reflect effective height.

 

 

Ceiling Firestop

44in.

(1118 mm) Effective Height

35 ft (10.7 m) max. straight unsupported chimney height

16.5ft (4.04 m) min. height/single offset-return 20 ft. (5.03 m) min. height/double offset-return

90 ft (27.43 m) max. height

Figure 8.2 Chimney Requirements

Heat & Glo • BAY-40, PIER-40 • 34977 • Rev AB 7/12

25

Page 25
Image 25
Heat & Glo LifeStyle PIER-40 owner manual A. Chimney Requirements