25Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. M • 7/12
Figure7.3

TopVent-HorizontalTermination

Ventingwith1elbow

H1
V1
VMinimum H1Maximum
90 Elbow 457 mm
305 mm (1 ft.) 914 mm (3 ft.)
457 mm (1.5 ft.) 1067 mm (3.5 ft.)
610 mm (2 ft.) 1.52 m (5 ft.)
762 mm (2.5 ft.) 1.85 m (6 ft.)
914 mm (3 ft.) 2.13 m (7 ft.)
1066 mm (3.5 ft.) 3.05 m (10 ft.)
1.2 m (4 ft.) 4.6 m (15 ft.)
H Max. =4.6 m (15 ft.)
V + H Max. = 12.2 m
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain specied clearances around venting and restop systems.
Install wall shield and ceiling restops as specied.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
Note: Use SLP Series
components only.
Note:All appliances that will burn butane must have

a 10 in. (254 mm) vertical section of pipe

before any other venting.