25Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. M • 7/12
Figure7.3
TopVent-HorizontalTermination
Ventingwith1elbow
H1
V1
VMinimum H1Maximum
90 Elbow 457 mm
305 mm (1 ft.) 914 mm (3 ft.)
457 mm (1.5 ft.) 1067 mm (3.5 ft.)
610 mm (2 ft.) 1.52 m (5 ft.)
762 mm (2.5 ft.) 1.85 m (6 ft.)
914 mm (3 ft.) 2.13 m (7 ft.)
1066 mm (3.5 ft.) 3.05 m (10 ft.)
1.2 m (4 ft.) 4.6 m (15 ft.)
H Max. =4.6 m (15 ft.)
V + H Max. = 12.2 m
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
• ALWAYS maintain specied clearances around venting and restop systems.
• Install wall shield and ceiling restops as specied.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
Note: Use SLP Series
components only.
Note:All appliances that will burn butane must have