29Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. M • 7/12
INSTALLED
HORIZONTALLY
H1

H2V1

V2
Figure7.9
TopVent-VerticalTermination
Ventingwith3elbows
Note: Use SLP Series
components only.
V1Minimum H1 + H2Maximum V2V1+V2Minimum
90° Elbow 1 ft. (305 mm) * *
1 ft. (305 mm) 2 ft (610 mm) * *
2 ft. (610 mm) 5 ft. (1.2 m) * *
3 ft. (914 mm) 6 ft. (1.8 m) * *
4 ft. (1.2 m) 14 ft. (4.3 m) * *
H Max. = 14 ft. (4.3 m)
V1 + V2 + H1 + H2 Max. = 40 ft. (12.2 m)
* No specic restrictions on this value EXCEPT V1 + V2 + H1 + H2 cannot exceed 40 ft. (12.2 m)
Note:All appliances that will burn butane must have
a 12 in. (305 mm) vertical section of pipe before
any other venting.