6.3.5 Abnormal noise

BHD-G Service Manual

Portable Dehumidifier with R-410A

Heat Controller, Inc.

6.3.5 Abnormal noise

Check whether the lines are vibrating or coming into contact with other lines or compressor

Check whether the noise is from inside the line.

6.3.6 Complaint and remedy

Complaint

Cause

Remedy

 

 

 

 

Transformer (Discharge

Check resistance between the two input/output lines on

No display or any button

transformer before

transformer. Replace the transformer if either of the input/

testing)

output is open or the transformer is damaged.

failure.

Display board or main

Replace the display board if it is +5V or else replace the

 

 

PCB failure.

main PCB.

 

No power

Check voltage at electrical outlet. Correct if none.

 

 

 

 

Power supply cord

Check voltage at the power cord terminal on Main PCB.

 

Replace the power cord if no voltage.

 

 

 

Transformer (Discharge

Check resistance between the two input/output lines on

 

transformer before

transformer. Replace the transformer if either of the input/

 

testing)

output is open or the transformer is damaged.

Fan motor will not run.

Wire disconnected or

Reconnect wire. Refer to wiring diagram for terminal

connection loose

identification. Repair or replace loose terminal.

 

 

Main PCB failure

Select fan speed and check the voltage of P1, P2 on main

 

PCB. Replace the main PCB if no voltage.

 

 

 

Capacitor (Discharge

Test capacitor. Replace if not within 10% of manufacturer’s

 

capacitor before testing)

rating. Replace if shorted, open or damaged.

 

 

Fan blade hitting shroud or blower hitting scroll. Realign

 

Will not rotate

assembly. Check fan motor bearings. Replace the motor if

 

 

motor shaft does not rotate.

 

 

Check voltage. Call an electrician if not with in limits.

 

 

Test capacitor. Replace if not within 10% of manufacturer’s

Fan motor runs intermittently

Revolves on over load.

rating. Replace if shorted, open or damaged.

Check bearings. Replace the motor if the fan blade can’t

 

 

rotate freely.

 

 

Pay attention to any change from high speed to low speed.

 

 

Replace the motor if the speed does not change.

Excessive noise

Copper tubing

Remove the cabinet and carefully rearrange tubing not to

contact cabinet, compressor, shroud and/or barrier.

 

 

 

 

The amount of the refrigerant is too much, making the

 

Refrigerant

compressor load too big. Recycle and recharge the

Stops instantly after startup.

 

refrigerant after checking the charge amount.

 

Compressor

The compressor overheated. Replace.

13