Heat Controller BHD-501-G Heat Controller, Inc, Portable Dehumidifier with R-410A, Complaint

Models: BHD-301-G BHD-651-G BHD-501-G

1 17
Download 17 pages 51.77 Kb
Page 15
Image 15

Heat Controller, Inc.

Portable Dehumidifier with R-410A

BHD-G Service Manual

 

 

 

 

 

 

 

 

Complaint

Cause

Remedy

 

 

 

 

 

Fan

Replace the fan if cracked, out of balance, or partially

 

missing.

 

 

 

 

 

Blower

Replace the blower if cracked, out of balance, or partially

Fan motor noise

missing.

 

 

 

Loose screws

Tighten them.

 

 

 

 

 

 

 

 

Replace the motor if knocking sounds continues when

 

Worn bearings

running, or if the motor hums or noise appears to be internal

 

 

while running.

 

 

Voltage

Check voltage. Call an electrician if not within limits.

 

 

 

 

 

Check the wire connections, if loose, repair or replace

 

Wiring

the terminal. If wires are off, refer to wiring diagram for

 

identification, and replace. Check wire locations. If not per

Compressor fan motor runs

 

 

wiring diagram, correct.

 

only

 

 

Main PCB failure

Replace the main PCB.

 

 

 

 

Capacitor (Discharge

Check the capacitor. Replace if not within 10% of

 

capacitor before testing)

manufacturer’s rating. Replace if shorted, open, or damaged.

 

Humidity sensor

Replace if shorted, open, or damaged.

 

Compressor

Check the compressor for open circuit or ground. If open or

 

grounded, replace the compressor.

 

 

 

 

 

Air filter

Clean if restricted.

 

 

Condenser and

Clean if restricted.

 

 

Evaporator

 

 

 

 

 

Fan motor

Check the fan capacitor and replace if not within 10% of

 

manufacturer’s rating.

 

 

 

 

 

Room structure

Ensure that the room the unit is operating in is sealed well.

 

Close any open doors or windows.

 

 

 

 

Insufficient capacity

Air flow

Clean or remove any barrier that blocks the inlet/outlet air

 

flow of the unit.

 

 

 

 

 

Less refrigerant

Check the lines for leakage. Recycle the refrigerant, correct

 

the leakage points and recharge.

 

 

 

 

 

Capillary tube

Regulate the flow of capillary tube and make the evaporating

 

temperature appropriate if the evaporator is frosted.

 

 

 

 

The inlet and outlet valve of the compressor is damaged,

 

 

making the low pressure connected with the high pressure.

 

Compressor

The refrigerating system is difficult to produce high pressure

 

 

and low pressure. Replace the compressor after checking

 

 

for the failure.

 

The compressor does not stop

Humidity sensor

Check and replace if the Humidity sensor, if open or

even if the room humidity has

 

damaged.

 

reached the set RH%.

 

 

 

Main PCB

Check and replace the main PCB

 

 

 

 

Power supply

The input power supply voltage is too low. Call an electrician

 

if not within limits.

 

The unit starts and stops

 

 

Humidity sensor

Check and replace if the Humidity sensor, if open or

frequently.

damaged.

 

 

 

 

Main PCB

Check and replace the main PCB.

 

 

 

 

 