Heat Controller HTS SERIES manual Ground-LoopHeat Pump Applications, Type, 10F -12.2C, 15F -9.4C

Models: HTS SERIES

1 44
Download 44 pages 17.62 Kb
Page 11
Image 11
Type

T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r

R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A

R e v. : 0 3 A u g u s t , 2 0 1 2

Ground-Loop Heat Pump Applications

Table 2: Approximate Fluid Volume (U.S. gal. [L]) per 100’ of Pipe

Fluid Volume (gal [liters] per 100’ [30 meters] Pipe)

Pipe

Size

Volume (gal) [liters]

 

1”

4.1 [15.3]

Copper

1.25”

6.4 [23.8]

 

2.5”

9.2 [34.3]

Rubber Hose

1”

3.9 [14.6]

 

3/4” IPS SDR11

2.8 [10.4]

 

1” IPS SDR11

4.5 [16.7]

 

1.25” IPS SDR11

8.0 [29,8]

Polyethylene

1.5” IPS SDR11

10.9

[40.7]

2” IPS SDR11

18.0

[67.0]

 

 

1.25” IPS SCH40

8.3 [30.9}

 

1.5” IPS SCH40

10.9

[40.7]

 

2” IPS SCH40

17.0

[63.4]

Unit Heat

Typical

1.0

[3.8]

Exchanger

 

 

 

Flush Cart Tank

10” Dia x 3ft tall

10 [37.9]

[254mm x 91.4cm tall]

 

 

 

Figure 4: Loop Connection (Indoor Compressor Section)

To Loop

Flow

Controller

Unit Power

Disconnect

Insulated

Hose Kit

AH & Thermostat Wiring 10°F [-12.2°C]

Air Pad or Extruded polystyrene insulation board

15°F [-9.4°C]P/T Plugs

NOTICE! Cabinet opening around loop piping (outdoor compressor section) must be sealed to prevent entry of rodents that could potentially damage unit wiring by chewing on the insulation.

Table 3: Antifreeze Percentages by Volume

Type

Minimum Temperature for Low Temperature Protection

10°F [-12.2°C]

15°F [-9.4°C]

20°F [-6.7°C]

25°F [-3.9°C]

 

Methanol

25%

21%

16%

10%

100% USP food grade Propylene Glycol

38%

25%

22%

15%

Ethanol*

29%

25%

20%

14%

* Must not be denatured with any petroleum based product

www.heatcontroller.com

11

Page 11
Image 11
Heat Controller HTS SERIES Ground-LoopHeat Pump Applications, Type, 10F -12.2C, 15F -9.4C, 20F -6.7C, 25F -3.9C, Methanol