Heat Controller HTS SERIES Functional Troubleshooting, Fault, Htg Clg, Possible Cause, Solution

Models: HTS SERIES

1 44
Download 44 pages 17.62 Kb
Page 40
Image 40
Htg Clg

HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS

R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A

R e v. : 0 3 A u g u s t , 2 0 1 2

Functional Troubleshooting

Fault

Htg Clg

Possible Cause

Solution

 

 

 

 

 

IFC Fault Code 13

X

X

Improper output setting

Verify the AO-2 jumper is in the PWM position

Internal Flow

 

 

 

 

 

 

No pump output signal

Check DC voltage between A02 and GND - should be

Controller Fault

 

 

 

 

 

 

between 0.5 and 10 VDC with pump active

 

 

 

Low pump voltage

Check line voltage to the pump

 

 

 

 

 

 

 

 

No pump feedback signal

Check DC voltage between T1 and GND. Voltage should

 

 

 

 

be between 3 and 4 VDC with pump OFF, and between

 

 

 

 

0 and 2 VDC with the pump ON

 

 

 

 

 

 

 

 

Bad pump RPM sensor

Replace pump if the line voltage and control signals are

 

 

 

 

present at the pump, and the pump does not operate

 

 

 

 

 

ESD - ERV Fault (DXM Only)

X

X

ERV unit has fault

Troubleshoot ERV unit fault

Green Status LED Code 3

(Rooftop units only)

 

 

 

 

 

 

 

 

No Fault Code Shown

X

X

No compressor operation

See 'Only Fan Operates'

X

X

Compressor overload

Check and replace if necessary

 

 

 

 

 

 

X

X

Control board

Reset power and check operation

 

X

X

Dirty air filter

Check and clean air filte r

 

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit

Unit Short Cycles

X

X

Unit selection

Unit may be oversized for space - check sizing for actual

 

load of space

 

 

 

 

 

 

 

 

 

 

X

X

Compressor overload

Check and replace if necessary

 

X

X

Thermostat position

Insure thermostat set for heating or cooling operation

 

X

X

Unit locked out

Check for lockout codes - reset power

Only Fan Runs

 

 

 

 

X

X

Compressor overload

Check compressor overload - replace if necessary

 

X

X

Thermostat wiring

Check thermostat wiring at DXM2 - put in Test Mode and

 

jumper Y1 and R to give call for compressor

 

 

 

 

 

 

 

 

 

40

Heat Controller, Inc. Water-Source Heating and Cooling Systems

Page 40
Image 40
Heat Controller HTS SERIES manual Functional Troubleshooting, Heat Controller, Inc. Water-Sourceheat Pumps, Fault, Htg Clg