Unit Start-Up and Operating Conditions
Unit and System Checkout
BEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT
Shutoff valves: Insure that all isolation valves are open.
Line voltage and wiring: Verify that voltage is within an acceptable range for the unit and wiring and fuses/breakers are properly sized. Verify that low voltage wiring is complete. Unit control transformer: Insure that transformer has the properly selected voltage tap. Residential
Antifreeze has been added if necessary.
Entering water and air: Insure that entering water and air temperatures are within operating limits of Tables 9a and 9b. Low water temperature cutout: Verify that low water temperature
HWG pump is disconnected unless piping is completed and air has been purged from the system.
Water flow balancing: Record inlet and outlet water temperatures for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water flow that could erode heat exchangers.
Unit air coil and filters: Insure that filter is clean and accessible. Clean air coil of all manufacturing oils.
Unit controls: Verify that DXM2 field selection options are properly set. Low voltage wiring is complete.
Blower CFM and Water ∆T is set on communicating thermostats or diagnostic tool.
Service/access panels are in place.
SYSTEM CHECKOUT
System water temperature: Check water temperature for proper range and also verify heating and cooling set points for proper operation.
System pH: Check and adjust water pH if necessary to maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fittings (see Table 4).
System flushing: Verify that all air is purged from the system. Air in the system can cause poor operation or system corrosion. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Some antifreeze solutions may require distilled water.
Internal Flow Controller: Verify that it is purged of air and in operating condition.
System controls: Verify that system controls function and operate in the proper sequence.
Low water temperature cutout: Verify that low water temperature
(LT1 - JW3).
Miscellaneous: Note any questionable aspects of the installation.
CAUTION!
CAUTION! Verify that ALL water valves are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
CAUTION!
CAUTION! To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless antifreeze is added to the water loop. Heat exchangers never fully drain by themselves and will freeze unless winterized with antifreeze.
Unit
1.Turn the thermostat fan position to “ON.” Blower should start.
2.Balance air flow at registers.
3.Adjust all valves to their full open position. Turn on the line power to all heat pump units.
4.Room temperature should be within the
5.It is recommended that
6.Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other factor must be at normal level to insure proper unit operation.
6.Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) entering water temperature. When either of the factors is at a minimum or maximum level, the other factor must be at normal levels to insure proper unit operation.
a.Place the unit in Manual Operation. When in manual mode activate Y1,Y2, and O to initiate the cooling mode. Also manually increase CFM until desired cooling CFM is achieved. Next adjust pump speed % until desired loop temperature difference (leaving water temperature minus entering water temperature) is achieved. (For modulating valve adjust valve %).
INSTALLER SETTINGS
THERMOSTAT CONFIG
SYSTEM CONFIG
ACCESSORY CONFIG
INPUT DEALER INFO
HUMIDITY CONFIG
TEMPERATURE ALGORITHM
DEMAND REDUCTION CNFG
SERVICE MODE
RESTORY DEFAULTS
ATC32U01
SELECT OPTION
PREVIOUS
30 | Heat Controller, Inc. |