Unit Start-Up and Operating Conditions

HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS

R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A

R e v. : 0 3 A u g u s t , 2 0 1 2

Unit Start-Up and Operating Conditions

Unit and System Checkout

BEFORE POWERING SYSTEM, please check the following:

UNIT CHECKOUT

Shutoff valves: Insure that all isolation valves are open.

Line voltage and wiring: Verify that voltage is within an acceptable range for the unit and wiring and fuses/breakers are properly sized. Verify that low voltage wiring is complete. Unit control transformer: Insure that transformer has the properly selected voltage tap. Residential 208-230V units are factory wired for 230V operation unless specified otherwise. Loop/water piping is complete and purged of air. Water/piping is clean.

Antifreeze has been added if necessary.

Entering water and air: Insure that entering water and air temperatures are within operating limits of Tables 9a and 9b. Low water temperature cutout: Verify that low water temperature cut-out on the DXM2 control is properly set. Unit fan: Manually rotate fan to verify free rotation and insure that blower wheel is secured to the motor shaft. Be sure to remove any shipping supports if needed. DO NOT oil motors upon start-up. Fan motors are pre-oiled at the factory. Check unit fan speed selection and compare to design requirements. Condensate line: Verify that condensate trap is installed and pitched.

HWG pump is disconnected unless piping is completed and air has been purged from the system.

Water flow balancing: Record inlet and outlet water temperatures for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water flow that could erode heat exchangers.

Unit air coil and filters: Insure that filter is clean and accessible. Clean air coil of all manufacturing oils.

Unit controls: Verify that DXM2 field selection options are properly set. Low voltage wiring is complete.

Blower CFM and Water ∆T is set on communicating thermostats or diagnostic tool.

Service/access panels are in place.

SYSTEM CHECKOUT

System water temperature: Check water temperature for proper range and also verify heating and cooling set points for proper operation.

System pH: Check and adjust water pH if necessary to maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fittings (see Table 4).

System flushing: Verify that all air is purged from the system. Air in the system can cause poor operation or system corrosion. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Some antifreeze solutions may require distilled water.

Internal Flow Controller: Verify that it is purged of air and in operating condition.

System controls: Verify that system controls function and operate in the proper sequence.

Low water temperature cutout: Verify that low water temperature cut-out controls are set properly

(LT1 - JW3).

Miscellaneous: Note any questionable aspects of the installation.

CAUTION!

CAUTION! Verify that ALL water valves are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.

CAUTION!

CAUTION! To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless antifreeze is added to the water loop. Heat exchangers never fully drain by themselves and will freeze unless winterized with antifreeze.

Unit Start-up Procedure

1.Turn the thermostat fan position to “ON.” Blower should start.

2.Balance air flow at registers.

3.Adjust all valves to their full open position. Turn on the line power to all heat pump units.

4.Room temperature should be within the minimum-maximum ranges of Table 9b. During start-up checks, loop water temperature entering the heat pump should be between 30°F [-1°C] and 95°F [35°C].

5.It is recommended that water-to-air units be first started in the cooling mode, when possible. This will allow liquid refrigerant to flow through the filter-drier before entering the TXV, allowing the filter-drier to catch any debris that might be in the system before it reaches the TXV.

6.Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other factor must be at normal level to insure proper unit operation.

6.Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) entering water temperature. When either of the factors is at a minimum or maximum level, the other factor must be at normal levels to insure proper unit operation.

a.Place the unit in Manual Operation. When in manual mode activate Y1,Y2, and O to initiate the cooling mode. Also manually increase CFM until desired cooling CFM is achieved. Next adjust pump speed % until desired loop temperature difference (leaving water temperature minus entering water temperature) is achieved. (For modulating valve adjust valve %).

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE ALGORITHM

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

ATC32U01

SELECT OPTION

INSTALLER SETTINGS PREVIOUS

30

Heat Controller, Inc. Water-Source Heating and Cooling Systems

Page 30
Image 30
Heat Controller HTS SERIES manual Unit Start-Upand Operating Conditions, Installer Settings Thermostat Config, Service Mode