6-6-6. Handling of Existing Pipe

6-6-6. Handling of Existing Pipe

When using the existing pipe, carefully check it for the following:

Wall thickness (within the specified range)

Scratches and dents

Water, oil, dirt, or dust in the pipe

Flare looseness and leakage from welds

Deterioration of copper pipe and heat insulator

Cautions for using existing pipe

Do not reuse the flare to prevent gas leak.

Replace it with the supplied flare nut and then process it to a flare.

Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean.

If discolored oil or much residue is discharged, wash the pipe.

Check welds, if any, on the pipe for gas leak.

When the pipe corresponds to any of the following, do not use it. Install a new pipe instead.

The pipe has been open (disconnected from indoor unit or outdoor unit) for a long period.

The pipe has been connected to an outdoor unit that does not use refrigerant R22, R410A or R407C.

The existing pipe must have a wall thickness equal to or larger than the following thickness.

Reference outside diameter

Wall thickness

(mm)

(mm)

 

 

Ø9.5

0.8

 

 

Ø15.9

1.0

 

 

Ø19.1

1.0

 

 

Never use any pipe with a wall thickness less than these thicknesses due to insufficient pressure capacity.

To use an existing Ø19.1 mm pipe, set bit 3 of SW802 (switch for existing pipe) on the P.C. board of the outdoor unit to ON.

In this case, the heating performance may be reduced depending on the outside air temperature and room temperature.

SW802

When shipped from factory

When using existing pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

ON

 

 

 

 

 

 

 

 

 

1

2

3

4

1

2

3

4

6-6-7. Recovery Method of Refrigerant

Use the refrigerant recovery switch SW801 on the P.C. board of the outdoor unit to recover refrigerant when the indoor unit or outdoor unit is moved.

Procedure

1.Turn on the power of the air conditioner.

2.Select the FAN mode for indoor unit operation with the remote controller.

3.Set SW804 on the P.C. board of the outdoor unit to all OFF, and then push SW801 for one second or more.

The air conditioner enters the forced cooling mode for up to 10 minutes.

Operation or handling the valve to recover refrigerant during this time period.

4.Upon completion of refrigerant recovery, close the valve and push SW801 for at least one second to stop operation.

5.Turn off the power.

ON

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

3

4

 

 

1

 

2

3

4

 

 

 

SW804

 

 

SW805

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

3

4

 

1

 

2

3

4

 

 

 

SW802

 

 

SW803

 

SW800 SW801 SW806

Existing pipe

Refrigerant

switch SW802

recovery switch

 

SW801

Cautions for using existing pipe DANGER

Take care for an electric shock because the P.C. board is electrified.

– 47 –

Page 47
Image 47
Toshiba RAV-SP1604AT8Z-E service manual Danger, Handling of Existing Pipe, Cautions for using existing pipe, Procedure, 47