Concealed Duct High Static Pressure | Installation Manual |
|
Procedure 6
When settings have been completed, push button to determine the settings.
When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the remote controller is accepted.)
!Filter sign setting
According to the installation condition, the filter sign term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(1 ∀ 2 ∀ 3 ∀ 4 ∀ 5 ∀ 6).
•For the CODE No. in Procedure 3, specify [01].
•For the [SET DATA] in Procedure 4, select the SET DATA of filter sign term from the following table.
SET DATA | Filter sign term | |
|
| |
0000 | None | |
|
| |
0001 | 150H | |
|
| |
0002 | 2500H | |
(Factory default) | ||
| ||
|
| |
0003 | 5000H | |
|
| |
0004 | 10000H | |
|
|
!To secure better effect of heating
When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling. Follow to the basic operation procedure
(1 ∀ 2 ∀ 3 ∀ 4 ∀ 5 ∀ 6).
•For the CODE No. in Procedure 3, specify [06].
•For the set data in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below.
SET DATA | Detection temperature shift value | |
|
| |
0000 | No shift | |
|
| |
0001 | +1°C | |
|
| |
0002 | +2°C | |
(Factory default) | ||
| ||
|
| |
0003 | +3°C | |
|
| |
0004 | +4°C | |
|
| |
0005 | +5°C | |
|
| |
0006 | +6°C | |
|
|
!Power saving mode
1.Push button for at least four seconds when the air conditioner is not working.
flashes.
Indicates CODE No. “C2.”
2.Select an indoor unit to be set by pushing (left side of the button).
Each time you push the button, unit numbers change as follows:
UNIT No. |
| UNIT No. |
| UNIT No. |
|
|
UNIT No.
The fan of the selected unit runs.
3.Adjust the power save setting by pushing TIME buttons.
Each push of the button changes the power level by 1% within the range from 100% to 50%.
* The factory default is 75%.
Setting of power level in power saving mode
4.Determine the setting by pushing button.
5.Push button to complete the setting.
– 29 – |