Toshiba RAV-SM2802DT-E Gas side refrigerant pipe connection, Evacuation, Tightening connection

Models: RAV-SM2242DT-E RAV-SM2802DT-E

1 41
Download 41 pages 43.38 Kb
Page 24
Image 24
Tightening connection

Concealed Duct High Static Pressure

Tightening connection

▼Tightening torque of flare pipe connections CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit: N•m)

 

 

Outer dia. of copper pipe

Tightening torque

 

 

12.7 mm (dia.)

50 to 62 (5.0 to 6.2 kgf•m)

 

 

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.

(Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union Do not burn the pipe heat insulator.!Gas side refrigerant pipe connectionPiping with outdoor unit!EvacuationFlare nut

Externally

 

 

Internally

 

threaded side

 

 

threaded side

 

 

 

 

 

 

Use a wrench to secure.

Use a torque wrench to tighten.

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

Installation Manual

Remove the cup on the gas side piping by using a brazing machine.

23-EN CAUTION

Do not burn the pipe heat insulator.

Remove the cap.

Attached joint part

Connection pipe Locally procured Ø28.6 mm

Braze the attached joint part to the gas side piping and braze the connection piping to the joint part.

brazing

Braze all around

brazing

Turn back the pipe heat insulator and tie up with a banding band.

Tie up with a banding

– 23 – band.

!Gas side refrigerant pipe connection

Turn up the pipe heat insulator to the unit side.

Wrap the pipe with wet cloth.

Piping with outdoor unit

For details of installation, refer to the Installation Manual of the outdoor unit.

!Evacuation

Wet cloth

Turn up pipe heat insulator

Remove the all brazed part.

Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.

For details, follow to the Installation Manual attached to the outdoor unit.

Never use the refrigerant sealed in the outdoor unit for evacuation.

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

23-EN

– 23 –

Page 24
Image 24
Toshiba RAV-SM2802DT-E Gas side refrigerant pipe connection, Evacuation, Tightening connection, Piping with outdoor unit