Toshiba RAV-SM2802DT-E Procedure, Concealed Duct High Static Pressure, Installation Manual, 33-EN

Models: RAV-SM2242DT-E RAV-SM2802DT-E

1 41
Download 41 pages 43.38 Kb
Page 34
Image 34
33-EN

Concealed Duct High Static Pressure

Installation Manual

 

Procedure 6

If there is other indoor unit to be changed, repeat procedure 2 to 5 to change the setup.

When the above setup has finished, push – 33 – to select the indoor UNIT No. before change of setup, specify CODE

No. [12], [13], [14] in order with TEMP. Manual background / Manual background buttons, and then check the changed contents.

Address change check Before change: [3-3-1] After change: [2-2-2]

Pushing Manual background button clears the contents of which setup was changed.

(In this case, procedure from 2 is repeated.)

Indoor UNIT No. before setup change is displayed.

Procedure 7

After check of the changed contents, push Manual background button. (Setup is determined.) When pushing Manual background button, the display disappears and the status becomes the usual stop status. (When pushing Manual background button the operation from the remote controller is not accepted for approx. 1 minute.)

*If the operation from the remote controller is not accepted

even 1 minute or more passed after pushing Manual background button, it is considered that the address setup is incorrect.

In this case, the automatic address must be again set up.

Therefore repeat procedure of the setup change from the Procedure 1.

To recognize the position of the corresponding indoor unit though the indoor UNIT No. is known

Check the position during operation stop. (Be sure to stop operation of the set.)

 

1

1,3

2

 

Procedure 1

Push simultaneously Manual background + Manual background buttons for 4 seconds or more.

After a while, the display part flashes and the display appears as shown below.

In this time, the position can be checked because fan of the indoor unit operate.

• For the group control, the indoor UNIT No. is displayed as

[Manual backgroundManual backgroundManual background ] and fans of all the indoor units in the group control operate.

Check the displayed CODE No. is [01].

When the CODE No. is other than [01], push Manual background button to erase the display and repeat procedure from the first step.

(After pushing Manual background button, operation of the remote controller is not accepted for approx. 1 minute.)

(* Display changes according to the model No. of indoor unit.)

Procedure 2

In the group control, every pushing Manual background button, the indoor UNIT No. in the group control is displayed in order. In this time, the position of the indoor unit can be confirmed because only fan of the selected indoor unit operate.

(For a group control, No. of the firstly displayed indoor unit becomes the header unit.)

Procedure 3

After confirmation, push Manual background button to return the mode to the usual mode.

When pushing Manual background button, the display disappears and the status becomes the usual stop status.

(When pushing Manual background button the operation from the remote controller is not accepted for approx. 1 minute.)

33-EN

– 33 –

Page 34
Image 34