!Remote controller switch monitoring function

Concealed Duct High Static Pressure

Installation Manual

 

!Remote controller switch monitoring function

This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.

2

4

1 3

 

Outdoor unit data

 

 

CODE No.

Data name

60

Outdoor unit heat exchanger (coil)

temperature (TE)

 

 

 

61

Outside air temperature (TO)

 

 

62

Compressor discharge temperature (TD)

 

 

63

Compressor suction temperature (TS)

 

 

64

 

 

65

Heatsink temperature (THS)

 

 

6A

Operating current (x1/10)

 

 

F1

Compressor cumulative operating hours

(x100h)

 

1.Push – 30 – and Manual background buttons simultaneously for at least 4 seconds to call the service monitor mode.

The service monitor indicator lights up and the

header indoor unit number is displayed first. CODE

EN

No.

is also displayed.

 

2.Pushing TEMP. Manual backgroundManual background buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)

3.Pushing Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background (left side of the button), select an indoor unit to be monitored. The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.

4.Push Manual background button to return to the normal display.

 

Indoor unit data

 

 

CODE No.

Data name

 

 

01

Room temperature (remote controller)

 

 

02

Indoor unit intake air temperature (TA)

 

 

03

Indoor unit heat exchanger (coil)

temperature (TCJ)

 

 

 

04

Indoor unit heat exchanger (coil)

temperature (TC)

 

 

 

F3

Indoor unit fan cumulative operating hours

(x1 h)

 

 

 

– 30 –