! Installation space

Concealed Duct High Static Pressure

Installation Manual

 

! Installation space

(Unit: mm)

 

 

Reserve space required for maintenance the indoor unit and service work.

200 or more Servicing space

Concealed duct high static pressure

Check port with carrying in port 600x600

<Installation example>

1000 or more

Air flow direction

 

Concealed

Filter chamber

 

duct high static

 

 

Air outlet chamber

pressure

 

 

Air inlet chamber

 

 

EN

Duct hose

Duct hose

Duct hose

Air flow direction

REQUIREMENT

1.Attach the optional accessories (drain-up kit etc.) on the unit before installing the unit. Also, set the check port with carrying in port to the side surface of the unit except air inlet panel.

2.Prepare the check port with carrying in port hole with the size of 600x600mm.

!Filter cleaning sign term setting

The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed according to the condition of installation.

For setup method, refer to “Filter sign setting” and “To secure better effect of heating” in the Applicable controls of this Manual.