Toshiba RAV-SM2242DT-E, RAV-SM2802DT-E Procedure example, Concealed Duct High Static Pressure

Models: RAV-SM2242DT-E RAV-SM2802DT-E

1 41
Download 41 pages 43.38 Kb
Page 33
Image 33
Procedure example 1

Concealed Duct High Static Pressure

Procedure example 1

Manual address setup procedure

While the operation stops, change the setup. (Be sure to stop the operation of the unit.)

Installation Manual

3.Push – 32 – button.

In this time, the setup finishes when the display changes from flashing to lighting.

Indoor unit No. before setup change is displayed.

 

 

7

3 -2,

 

3 -1,

4 -2,

 

4 -1,

5 -2

 

5 -1,

 

 

6

7

 

3 -3,

 

 

 

 

4 -3,

1

2,6

5 -3,

 

Procedure 1

Push simultaneously Manual background + Manual background + Manual background buttons for 4 seconds or more. After a while, the display part flashes as shown below. Check the displayed CODE No. is [10].

• When the CODE No. is other than [10], push

button to

erase the display and repeat procedure from the first step.

Procedure 4

1.Using TEMP. Manual background / Manual background buttons, specify CODE No. [13].

(CODE No. [13]: Indoor address)

2.Using TIME Manual background / Manual background buttons, change the indoor address from [3] to [2].

3.Push Manual background button.

In this time, the setup finishes when the display changes from flashing to lighting.

(After pushing

button, operation of the remote

controller is not accepted for approx. 1 minute.)

(For a group control, No. of the firstly displayed indoor unit

becomes the header unit.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(* Display changes according to the model No. of indoor unit.)

Procedure 2

Indoor unit No. before setup change is displayed.

Procedure 5

EN

Every pushing Manual background button, the indoor UNIT No. in the group control is displayed in order. Select the indoor unit of which setup is changed.

In this time, the position of the indoor unit of which setup is changed can be confirmed because fan of the selected indoor unit operate.

Procedure 3

1.Using TEMP. Manual background / Manual background buttons, specify CODE No. [12].

(CODE No. [12]: Line address)

2.Using TIME Manual background / Manual background buttons, change the line address from [3] to [2].

1.Using TEMP. Manual background / Manual background buttons, specify CODE No. [14].

(CODE No. [14]: Group address)

2.Using TIME Manual background / Manual background buttons, change the SET DATA from [0001] to [0002].

(SET DATA [Header unit: 0001] [Follower unit: 0002])

3.Push Manual background button.

In this time, the setup finishes when the display changes from flashing to lighting.

Indoor UNIT No. before setup change is displayed.

– 32 –

32-EN

Page 33
Image 33