Toshiba RAV-SM2802DT-E Error codes and parts to be checked, Concealed Duct High Static Pressure

Models: RAV-SM2242DT-E RAV-SM2802DT-E

1 41
Download 41 pages 43.38 Kb
Page 40
Image 40
!Error codes and parts to be checked

Concealed Duct High Static Pressure

Installation Manual

 

!Error codes and parts to be checked

Wired remote

 

 

 

 

controller

Main defective parts

Judging device

Parts to be checked / error description

Air conditioner

display

status

Indication

 

 

 

 

 

No header remote controller

 

Incorrect remote controller setting --- The header remote controller has

 

 

Remote

not been set (including two remote controllers).

 

E01

 

*

 

 

Remote controller

controller

No signal can be received from the indoor unit.

 

 

 

 

 

 

communication error

 

 

 

 

 

 

 

 

 

 

 

E02

Remote controller transmission

Remote

System interconnecting wires, indoor P.C. board, remote controller

*

error

controller

--- No signal can be sent to the indoor unit.

 

 

 

 

 

 

 

E03

Indoor unit-remote controller

Indoor

Remote controller, network adapter, indoor P.C. board --- No data is

Auto-reset

regular communication error

received from the remote controller or network adapter.

 

 

 

 

 

 

 

 

 

Indoor unit-outdoor unit serial

 

System interconnecting wires, indoor P.C. board, outdoor P.C. board -

 

E04

communication error

Indoor

Auto-reset

 

 

 

-- Serial communication error between indoor unit and outdoor unit

 

 

IPDU-CDB communication error

 

 

 

 

 

 

 

 

 

 

 

E08

Duplicated indoor addresses

Indoor

Indoor address setting error --- The same address as the self-address

Auto-reset

 

 

 

was detected.

 

 

 

 

Remote controller address setting error --- Two remote controllers are

 

E09

Duplicated header remote

Remote

set as header in the double-remote controller control.

*

 

controllers

controller

(* The header indoor unit stops raising alarm and follower indoor units

 

 

 

 

 

 

 

 

 

continue to operate.)

 

 

 

 

 

 

E10

CPU-CPU communication error

Indoor

Indoor P.C. board --- Communication error between main MCU and

Auto-reset

motor microcomputer MCU

 

 

 

 

 

 

 

 

 

 

Header indoor unit-indoor

 

Indoor P.C. board --- Regular communication is not possible between

 

E18

follower unit regular

Indoor

header and follower indoor units or between twin header (main) and

Auto-reset

 

communication error

 

follower (sub) units.

 

 

 

 

 

 

E31

IPDU communication error

Outdoor

Communication error between IPDU and CDB

Entire stop

 

 

 

 

 

F01

Indoor unit heat exchanger

Indoor

Heat exchanger sensor (TCJ), indoor P.C. board --- Open-circuit or

Auto-reset

sensor (TCJ) error

short-circuit of the heat exchanger sensor (TCJ) was detected.

 

 

 

 

 

 

 

 

F02

Indoor unit heat exchanger

Indoor

Heat exchanger sensor (TC), indoor P.C. board --- Open-circuit or

Auto-reset

sensor (TC) error

short-circuit of the heat exchanger sensor (TC) was detected.

 

 

 

 

 

 

 

 

F04

Outdoor unit discharge temp.

Outdoor

Outdoor temp. sensor (TD), outdoor P.C. board --- Open-circuit or

Entire stop

sensor (TD) error

short-circuit of the discharge temp. sensor was detected.

 

 

 

 

 

 

 

 

F06

Outdoor unit temp. sensor (TE/

Outdoor

Outdoor temp. sensors (TE/TS), outdoor P.C. board --- Open-circuit or

Entire stop

 

TS) error

 

short-circuit of the heat exchanger temp. sensor was detected.

 

 

 

 

 

 

F07

TL sensor error

Outdoor

TL sensor may be displaced, disconnected or short-circuited.

Entire stop

 

 

 

 

 

F08

Outdoor unit outside air temp.

Outdoor

Outdoor temp. sensor (TO), outdoor P.C. board --- Open-circuit or

Operation

sensor error

short-circuit of the outdoor air temp. sensor was detected.

continued

 

 

 

 

 

 

 

F10

Indoor unit room temp. sensor

Indoor

Room temp. sensor (TA), indoor P.C. board --- Open-circuit or short-

Auto-reset

(TA) error

circuit of the room temp. sensor (TA) was detected.

 

 

 

 

 

 

 

 

F12

TS (1) sensor error

Outdoor

TS (1) sensor may be displaced, disconnected or short-circuited.

Entire stop

 

 

 

 

 

F13

Heat sink sensor error

Outdoor

Abnormal temperature was detected by the temp. sensor of the IGBT

Entire stop

 

 

 

heat sink.

 

 

 

 

 

 

F15

Temp. sensor connection error

Outdoor

Temp. sensor (TE/TS) may be connected incorrectly.

Entire stop

 

 

 

 

 

F29

Indoor unit, other P.C. board

Indoor

Indoor P.C. board --- EEPROM error

Auto-reset

error

 

 

 

 

 

 

 

 

 

F31

Outdoor unit P.C. board

Outdoor

Outdoor P.C. board ---- In the case of EEPROM error.

Entire stop

 

 

 

 

 

 

Outdoor unit compressor

 

Current detect circuit, power voltage --- Minimum frequency was

 

H01

Outdoor

reached in the current releasing control or short-circuit current (Idc)

Entire stop

breakdown

 

 

after direct excitation was detected

 

 

 

 

 

 

 

 

 

 

H02

Outdoor unit compressor lock

Outdoor

Compressor circuit --- Compressor lock was detected.

Entire stop

 

 

 

 

 

H03

Outdoor unit current detect circuit

Outdoor

Current detect circuit, outdoor unit P.C. board --- Abnormal current was

Entire stop

 

error

 

detected in AC-CT or a phase loss was detected.

 

 

 

 

 

 

H04

Case thermostat operation (1)

Outdoor

Malfunction of the case thermostat

Entire stop

 

 

 

 

 

 

Outdoor unit low-pressure

 

Current, high-pressure switch circuit, outdoor P.C. board --- Ps

 

H06

Outdoor

pressure sensor error was detected or low-pressure protective

Entire stop

system error

 

 

operation was activated.

 

 

 

 

 

 

 

 

 

 

L03

Duplicated header indoor units

Indoor

Indoor address setting error --- There are two or more header units in

Entire stop

 

 

 

the group.

 

L07

Group line in individual indoor

Indoor

Indoor address setting error --- There is at least one group-connected

Entire stop

 

unit

 

indoor unit among individual indoor units.

 

L08

Indoor group address not set

Indoor

Indoor address setting error --- Indoor address group has not been set.

Entire stop

 

 

 

 

 

L09

Indoor power level not set

Indoor

Indoor power level has not been set.

Entire stop

 

 

 

 

 

L10

Outdoor unit P.C. board

Outdoor

In the case of outdoor P.C. board jumper wire (for service) setting error

Entire stop

 

 

 

 

 

39-EN

– 39 –

Page 40
Image 40