Toshiba RAV-SM2242DT-E Wire connection, Concealed Duct High Static Pressure, Installation Manual

Models: RAV-SM2242DT-E RAV-SM2802DT-E

1 41
Download 41 pages 43.38 Kb
Page 27
Image 27
!Wire connection

Concealed Duct High Static Pressure

Installation Manual

 

!Wire connection

REQUIREMENT

Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.

Be sure to pass the wires through the bushing of wire connection holes of the indoor unit.

Keep a margin (Approx. 100mm) on a wire to hang down the electrical control box at servicing, etc.

The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)

1.Remove the cover of the electrical control box by taking off the mounting screws (2 positions)

2.Tighten the screws of the terminal block, and fix the wires with cord attached to the electrical control box. (Do not apply tension to the connecting section of the terminal block.)

3.Mount the cover of the electrical control box without pinching wires.

<Terminal block of electrical control box>

 

System

Wired remote controller

Electrical

 

control box

 

interconnecting

connecting Terminal

Indoor fan power

cover

Terminal block

block

 

supply Terminal

 

 

 

block

 

 

 

 

 

 

Fixing screw

Bushing

Indoor fan power supply wire

System interconnecting wire

EN

Wired remote controller wire

Cord clamp

– 26 –

26-EN

Page 27
Image 27
Toshiba RAV-SM2242DT-E Wire connection, Concealed Duct High Static Pressure, Installation Manual, Requirement