Toshiba RAV-SM2802DT-E Wire connection change of fan motor, Concealed Duct High Static Pressure

Models: RAV-SM2242DT-E RAV-SM2802DT-E

1 41
Download 41 pages 43.38 Kb
Page 18
Image 18
!Wire connection change of fan motor

Concealed Duct High Static Pressure

Installation Manual

 

!Wire connection change of fan motor

This duct is composed of 3 fan motors.

To change external static pressure by duct resistance, connect the 3 connectors of the orange lead wires that are connected to the underside of the fan tap changing terminal block to the same number (F1, F2 or F3) terminal.

The wires of the fan motor has been connected to (F2) [External static pressure 137Pa (14mmAq)] as factory default.

Low static pressure (F1)

FM

FM

 

 

 

 

 

 

 

Fan motor

YEL

BLU

ORG

Fan motor

 

 

 

 

 

 

 

 

 

 

 

YEL

BLU

ORG

FM

Fan motor

YEL: Yellow

BLU: Blue

ORG: Orange

YEL

 

BLU

ORG

 

 

 

 

 

F1 F2 F3 F4

F1 F2 F3 F4

F1 F2 F3 F4

 

 

 

 

 

 

 

ORG

 

 

 

 

 

 

ORG

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN3

 

 

 

 

FAN2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard (Middle) static pressure (F2)

ORG

FAN1

Fan tap changing terminal block

FM

Fan motor

FM

FM

 

 

Fan motor

 

 

ORG

Fan motor

 

ORG

YEL

BLU

ORG

YEL

BLU

YEL

BLU

F1 F2 F3 F4

F1 F2 F3 F4

F1 F2 F3 F4

ORG

 

FAN3

ORG

 

FAN2

ORG

 

FAN1

Electrical control box

Control

P.C. board 17-EN

4P terminal block

3P terminal

2P terminal block block

High static pressure (F3)

FM

Fan motor

FM

Fan motor

FM

Fan motor

YEL

BLU

ORG

YEL

BLU

ORG

YEL

BLU

ORG

F1 F2 F3 F4

 

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN3

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN2

 

 

 

 

 

 

 

 

F1 F2 F3 F4

 

 

 

 

 

 

 

ORG

 

 

 

 

 

FAN1

 

 

 

 

 

 

 

 

Terminal block No.

Fan motor wiring

External static pressure

Remarks

Pa (mmAq)

 

 

 

 

 

 

 

 

F1

Yellow

69

(7)

 

Low static pressure

 

 

 

 

 

 

 

 

 

 

F2

Blue

137

(14)

Factory default

Middle static pressure

 

 

 

 

 

 

 

 

 

F3

Orange

196

(20)

 

High static pressure

 

 

 

 

 

 

 

 

 

 

* Do not use F4.

NOTE

When the external static pressure is changed, write down the static pressure once change in the wiring diagram of the indoor unit is made.

17-EN