Carrier 58HDV installation instructions Confined Space Installation, Requirements, Outside Air

Models: 58HDV

1 52
Download 52 pages 46.64 Kb
Page 9
Image 9
Confined Space Installation

Confined Space Installation

a. One opening MUST commence within 12(304.8mm)

NOTE: A confined space is defined as an area with less than 50

of the floor and the second opening MUST commence

within 12(304.8mm) of the ceiling.

cubic feet (1.43M)per 1,000 BTUH (2.33 cm2/kW) input rating for

b. Size openings and ducts per Table 1.

all gas appliances installed in the area.

c. Horizontal duct openings require 1 square inch of free

Requirements

area per 2,000 BTUH (11 cm2/kW) of combined input

1. Provide the space with sufficient air for proper combustion

for all gas appliances in the space (see Table 1).

d. Vertical duct openings or openings directly

and ventilation of flue gases using horizontal or vertical

communicating with the outdoors require 1 square inch

ducts or openings.

of free area per 4,000 BTUH (5.5 cm2/kW) for

2. Fig. 6 illustrates how to provide combustion and ventilation

combined input of all gas appliances in the space (see

air. A minimum of two permanent openings, one inlet and

Table 1).

one outlet, are required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This installation NOT approved in Canada

Gas Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gable Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Vent

Ventilated Attic

 

 

 

 

 

 

Top Above Insulation

 

Gable Vent

 

 

 

 

Alternate Inlet Air (1)

 

 

 

 

 

 

Gas Vent

 

Outlet

Outlet

 

 

Ventilated Attic

 

Air (1)

Outlet Air (1)

Soffit Vent

 

Air (2)

Top Above Insulation

 

 

 

 

 

 

 

 

 

 

 

 

OutletAir (1)

Soffit Vent

Inlet

Inlet

 

 

Air (1)

 

 

 

 

 

Air (2)

 

 

 

 

 

 

 

 

 

Inlet

 

Minimum One Inlet and One Outlet Air Supply is Required

 

 

 

 

May be in any Combination Shown

 

 

Inlet

 

Air (2)

 

Inlet Air Opening Must be Within12of floor

 

Ventilated Crawl Space

 

 

 

 

 

 

 

Outlet Air Opening Must be Within12of ceiling

 

alternate Inlet Air (1)

Air (1)

 

 

 

 

 

 

 

 

(1) 1 Square Inch per 4000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

(2) 1 Square Inch per 2000 BTUH

 

 

 

 

 

 

 

A07704

Fig. 6 - Outside Air

(This is ONLY a guide. Subject to codes of country having jurisdiction).

58HDV

3.One opening MUST be within 12(304.8mm) of the floor and the second opening within 12(304.8mm) of the ceiling.

a.1 sq. in of free area per 3,000 BTUH (7 cm2/kW) for combined input of all gas appliances in the space (see Table 1) and

b.not less than the sum of the areas of all vent connectors in the space.

The opening shall commence within 12(304.8mm) of the top of the enclosure. Appliances shall have clearances of at least 1(25.4mm) from the sides and back and 6(152.4mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

4.Size openings and ducts per Table 1.

a.Indoor openings that comply with the Indoor Combustion Air Method below and

b.Outdoor openings located as required in the Outdoor Combustion Air Method above and

c.Outdoor openings sized as follows.

(1.) Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method.

(2.) Outdoor opening size reduction Factor is 1 minus the Ratio in 1) above.

(3.) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor.

5.Horizontal duct openings require 1 square inch of free area per 2,000 BTUH of combined input for all gas appliances in area (see Table 1).

6.Vertical duct openings or openings directly to outside require 1 square inch of free area per 4,000 BTUH (5.5 cm2/kW) for combined input of all gas appliances in area (see Table 1).

9

Page 9
Image 9
Carrier 58HDV installation instructions Confined Space Installation, Requirements, Outside Air