Using Exterior Risers

1.Install elbows and pipe to form riser as shown in Fig. 23

2.Secure vent pipe to wall with galvanized strap or other rust resistant material to restrain pipe from moving.

3.Insulate pipe with Armaflex or equivalent moisture resistant closed cell foam insulation or Fiberglass insulation if boxed in and sealed against moisture.

Vertical Termination

1. Fig. 25 shows the proper installation and clearances for

vertical vent termination. The vertical roof termination

should be sealed with a plumbing roof boot or equivalent

flashing. The inlet of the intake pipe and end of the exhaust

OVERHANG

EXHAUST 12(304.8mm) MIN.

90°

INLET

12(304.8mm) MIN. Ground

Level OR Snow Level

25- 23- 73

vent must be terminated no less than 12(307.8mm) above

the roof or snow accumulation level, and 12(307.8mm)

away from a vertical wall or other protrusion.

2. If the vent system is installed in an existing chimney make

sure clearances shown in Fig. 25 are maintained. Horizontal

section before the termination elbow can be extended on the

inlet air to provide necessary clearance.

Vent Termination Shielding

Under certain wind conditions some building materials may be affected by flue products expelled in close proximity to unprotected surfaces. Sealing or shielding of the exposed surfaces with a

FRONT VIEW

Same Joist

Space

SIDE VIEW

12(304.8mm) MIN.

A07699

58HDV

corrosion resistant material (such as aluminum sheeting) may be required to prevent staining or deterioration. The protective material should be attached and sealed (if necessary) to the building before attaching the vent terminal.

Multi Vent Termination Clearances

When two (2) or more furnaces are vented near each other, each furnace must be individually vented.

Two (2) vent terminations may be installed as shown in Fig. 26, 27, 28, 29, and 30 but the next vent termination must be at least 36(914.4mm) away from first two terminations. It is important that vent terminations be made as shown to avoid recirculation of flue gases.

Fig. 24 - Recommended Alternate Installation

for Sustained Cold Weather

(0_F (-17_C) & below for 24 or more consecutive hours)

B

A

8” (203.2mm)* MIN. 20’ (6.1m) MAX

*18(457.2mm) Minimum for cold climates [sustained 0_F (- 17_C) and below for 24 or more consecutive hours]

8” (203.2mm) MIN.

12 ” (304.8mm)

MIN.

GRADE LEVEL

 

OR

 

SNOW LEVEL

25--00--04F

A07716

A

25--00--06

A = 12(304.8mm) Above roof or snow accumulation level B = 8(203.2mm) Min., 20(6.1m) Maximum, except in areas with extreme cold temperatures [sustained 0°F(-17°C) and below for 24 or more consecutive hours], the 18(457.2mm)

Min.

A07717

Fig. 25 - Rooftop Termination

Fig. 23 - Sidewall Termination with Exterior Risers to Get

Above Snow Level or Grade Level

29

Page 29
Image 29
Carrier 58HDV Using Exterior Risers, Vertical Termination, Vent Termination Shielding, Multi Vent Termination Clearances