Table 1

 

Free Area

 

 

 

 

 

 

 

 

 

 

Minimum Free Area Required for Each Opening or Duct to Outdoors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTUH (kW)

 

Two Horizontal Ducts

 

 

Single Opening

 

Two Vertical Ducts or

Round Duct

Input Rating

 

BTUH (kW)

 

 

BTUH (kW)

 

Openings

BTUH (kW)

 

 

sq. in./2,000(1 cm2/.09)

 

 

sq. in./3,000 (1 cm2/.135)

 

BTUH (kW)

sq.

 

 

 

 

 

sq. in./4,000(1 cm2/.18)

in./4,000(6.5cm2/.18)

 

 

 

 

 

 

 

40,000 (11.72)

 

20 sq. in. (129 cm2)

 

 

13.34 sq. in. (86 cm2)

 

10 sq. in. (65 cm2)

4(101.6mm)

50,000 (14.65)

 

25 sq. in. (161 cm2)

 

 

16.7 sq. in. (108 cm2)

 

12.5 sq. in. (81 cm2)

4(101.6mm)

60,000 (17.58)

 

30 sq. in. (194 cm2)

 

 

20 sq. in. (129 cm2)

 

15 sq. in. (97 cm2)

5(127mm)

75,000 (21.98)

 

37.5 sq. in. (242 cm2)

 

 

25 sq. in. (161 cm2)

 

18.75 sq. in. (121 cm2)

5(127mm)

80,000 (23.45)

 

40 sq. in. (258 cm2)

 

 

26.7 sq. in. (172 cm2)

 

20 sq. in. (129 cm2)

5(127mm)

100,000 (29.31)

 

50 sq. in. (322 cm2)

 

 

33.3 sq. in. (215 cm2)

 

25 sq. in. (161 cm2)

6(152.4mm)

125,000 (36.63)

 

62.50 sq. in. (403 cm2)

 

 

41.7 sq. in. (269 cm2)

 

31.25 sq. in. (202 cm2)

7(177.8mm)

EXAMPLE: Determining Free Area

 

 

 

 

 

 

Furnace

 

Water Heater

 

 

Total Input

 

 

 

100,000

+

30,000

=

(130,000 ÷ 4,000)

=

32.5 Sq. In. Vertical

 

29.31

 

8.8

 

(38.11 ÷ .18)

=

210 cm2 Vertical

 

Furnace

 

Water Heater

 

 

Total Input

 

 

 

100,000

+

30,000

=

(130,000 ÷ 2,000)

=

65 Sq. In. Horizontal

 

29.31

 

8.8

 

(38.11 ÷ .09)

=

423 cm2 Horizontal

 

Indoor Combustion Air (Unconfined Space)

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Most homes will require additional air from outdoors for combustion and ventilation. A space with at least 50 cubic feet (1.43M) per 1,000 (2.33 cm2/kW) Btuh Input rating or homes with tight construction may need outdoor air, supplied through ducts, to supplement air infiltration for proper combustion and ventilation of flue gasses.

Standard and Known- Air- Infiltration Rate Methods

©NFPA & AGA

Indoor air is permitted for combustion and ventilation, if the Standard or Known-Air-Infiltration Rate Method is used.

The Standard Method may be used, if the space has no less volume than 50 cubic feet per 1,000 BTUH input rating for all gas

appliances installed in the space. The standard method permits indoor air to be used for combustion and ventilation air.

The Known Air Infiltration Rate Method shall be used if the infiltration rate is known to be less than 0.40 air changes per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and add the volumes together to get the total minimum required volume for the space.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to supply additional air by means of ventilation grilles or ducts could result in personal injury or death.

An unconfined space or homes with tight construction may not have adequate air infiltration for proper combustion and ventilation of flue gasses. Most homes will require additional air.

 

Table 2

 

MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS

 

 

 

Other Than Fan- Assisted Total

 

 

Fan- assisted Total

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30,000 BTU

40,000 BTU

50,000 BTU

50,000 BTU

75,000

100,000 BTU

125,000 BTU

ACH

 

 

(8,790 kW)

(11,720 kW)

(14,650 kW)

(14,650 kW)

(21,975 kW)

(29,300 kW)

(36,625 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ft3 (m3)

 

 

 

 

0.60

 

 

1,050 (29.7)

1,400 (39.2)

1,750

(49)

1,250 (35)

1,875 (52.5)

2,500

(70)

3,125 (87.5)

 

 

 

 

 

 

 

 

 

 

 

0.50

 

 

1,260 (35.3)

1,680 (47.04)

2,100 (58.8)

1,500 (42)

2,250 (63)

3,000

(84)

3,750 (105)

 

 

 

 

 

 

 

 

 

 

0.40

 

 

1,575 (44.1)

2,100 (58.8)

2,625 (73.5)

1,875 (52.5)

2,813 (78.8)

3,750 (105)

4,688 (131.3)

 

 

 

 

 

 

 

 

 

 

 

0.30

 

 

2,100 (58.8)

2,800 (78.4)

3,500

(98)

2,500 (70)

3,750 (105)

5,000 (140)

6,250 (175)

 

 

 

 

 

 

 

 

 

 

0.20

 

 

3,150 (88.2)

4,200 (117.6)

5,250 (147)

3,750 (105)

5,625 (157.5)

7,500 (210)

9,375 (262.5)

 

 

 

 

 

 

 

 

 

 

 

 

0.10

 

 

6,300 (176.4)

8,400 (235.2)

10,500

(294)

7,500 (210)

11,250 (315)

15,000

(420)

18,750 (525)

 

 

 

 

 

 

 

 

 

 

0.00

 

 

NP

NP

NP

NP

NP

NP

NP

 

 

 

 

 

 

 

 

 

 

 

 

 

ACH = Air Changes per Hour NP = Not Permitted

Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54---2006, 9.3.2.2:

1. For appliances other than fan-assisted appliances (such as

 

 

 

(

 

 

)

a draft hood-equipped water heater), calculate using the fol-

Required Volume other

 

21 ft3

I

other

lowing equation:

²

 

 

 

1000 Btu / hr

ACH

 

 

 

 

 

 

 

 

10

Page 10
Image 10
Carrier 58HDV installation instructions Indoor Combustion Air Unconfined Space