58HDV
SEQUENCE OF OPERATION & DIAGNOSTICS
The following is the normal operating sequence at factory default settings (SW1 OFF/ON/OFF, SW2 all OFF)
NOTE: SW1 DIP switches (G, Y/Y2, W1, W2 thermostat terminals) and DEHUM (1/4” male quick connect terminal) are located on the FCB.
SW2 DIP switches and Y1 and O thermostat terminals are located on the TSIB.
Low Cooling (Y1) Request:
24VAC signals applied to Y1 & G terminals of TSIB (Tap Select Interface Board) and FCB (Furnace Control Board), respectively.
SLow Cooling motor speed is energized after 5 second Cool Fan On Delay time. Y1 & G signals removed from TSIB and FCB
SLow Cooling motor speed is
requests:
S24 VAC signals applied to Y1, DEHUM & G terminals of TSIB and FCB.
SSame operation as the cooling (Y1) request, except the cooling airflow is reduced 20% to compensate for high humidity conditions during cooling operation. The low cooling airflow returns to the normal setting after the DEHUM signal is removed.
High Cooling (Y1 & Y/Y2) or (Y/Y2) Request:
24VAC signals applied to Y1 & Y/Y2 & G or Y/Y2 & G terminals of FCB (Furnace Control Board).
SHigh Cooling motor speed is energized after 5 second Cool Fan On Delay time.
Y1 & Y/Y2 & G or Y/Y2 & G signals removed from TSIB and FCB
SHigh Cooling motor speed is
High Cooling (Y1 & Y/Y2 or Y/Y2) and dehumidification (DEHUM) requests:
S24 VAC signals applied to Y1 & Y/Y2 or Y/Y2, DEHUM, & G terminals of TSIB and FCB.
SSame operation as the high cooling (Y1 & Y/Y2 or Y/Y2) request, except the cooling airflow is reduced 20% to compensate for high humidity conditions during cooling operation. The high cooling airflow returns to the normal setting after the DEHUM signal is removed.
Low or high cooling and O terminal (Heat Pump mode):
SIf the J2 jumper is in the AC/HP EFFICIENCY position, there will be no change in blower airflow regardless of the O terminal being energized or
SIf the J2 jumper is in the HP COMFORT position, then there will be a 10% reduction in airflow when the O terminal is
NOTE 1) The motor has been set up to recognize the O terminal as energized during cooling calls (reversing valve energized for cooling).
Continuous Circulating Fan (G) Request:
24VAC signal applied to G terminal of FCB.
SContinuous fan speed is energized without delay.
G signal removed from FCB.
SContinuous fan speed is
NOTE 2) Heat or Cooling requests received during a Fan request, cause the fan speed to change to the appropriate heat or cool speed after the Fan On Delay time expires. The fan returns to continuous circulating speed after the selected Fan Off Delay time expires following loss of the Heating or Cooling request.
NOTE 3)
NOTE 4) Continuous blower selection DIP 10 and 11 will cause the blower to run in high cooling speed for all low cooling (Y1) calls. Continuous blower DIP settings of 00 and 01 will allow low cooling (Y1) calls to operate normally.
Heating (W1) Request (single stage thermostat operation, SW1 DIP switch #3 on the FCB must be in OFF position) (see furnace wiring diagram):
24VAC signal applied to W1 terminal of FCB.
SInducer motor turns on at high speed.
SFollowing a 15 second prepurge delay after the low pressure switch closes, the igniter begins a 17 second warm up. S The gas valve is energized, the main burners light at Low Heat rate.
S The igniter is
S The FCB will delay Low Heat blower operation for the
high pressure switch, then the High Heat solenoid energizes, and the fan switches to High Heat speed.
W1 signal removed from FCB.
SThe gas valve
SThe inducer runs at its present speed for a 15 second postpurge period. S The fan runs at its present speed.
S The blower
46