Temperature sensor

Temperature – Resistance value characteristic table

TA, TC, TCJ, TE, TS, TO sensors Representative value

Temperature

Resistance value (kΩ)

(°C)

(Minimum value)

(Standard value)

(Maximum value)

 

 

 

 

0

32.33

33.80

35.30

10

19.63

20.35

21.09

 

 

 

 

20

12.23

12.59

12.95

 

 

 

 

25

9.75

10.00

10.25

30

7.764

7.990

8.218

 

 

 

 

40

5.013

5.192

5.375

 

 

 

 

50

3.312

3.451

3.594

60

2.236

2.343

2.454

 

 

 

 

70

1.540

1.623

1.709

 

 

 

 

80

1.082

1.146

1.213

90

0.7740

0.8237

0.8761

 

 

 

 

100

0.5634

0.6023

0.6434

 

 

 

 

TD,TL sensors

Representative value

Temperature

Resistance value (kΩ)

(°C)

(Minimum value)

(Standard value)

(Maximum value)

 

 

 

 

0

150.5

161.3

172.7

10

92.76

99.05

105.6

 

 

 

 

20

58.61

62.36

66.26

 

 

 

 

25

47.01

49.93

52.97

30

37.93

40.22

42.59

 

 

 

 

40

25.12

26.55

28.03

 

 

 

 

50

17.00

17.92

18.86

60

11.74

12.34

12.95

 

 

 

 

70

8.269

8.668

9.074

 

 

 

 

80

5.925

6.195

6.470

90

4.321

4.507

4.696

 

 

 

 

100

3.205

3.336

3.468

 

 

 

 

Resistance (kΩ)

TA, TC, TCJ, TE, TS, TO sensors

40

30

20

10

0

010 20 30 40 50 60 70 80 90 100 Temperature (˚C)

Output voltage (V)

TD,TL sensors

Resistance (kΩ) (50˚C or lower)

200

150

100

50

0

0 10 20 30

40 50 60 70 80 90 100

20

or higher)

15

10

) (50˚C

0

(kΩ

Resistance

5

 

Temperature (˚C)

As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the resistance value cannot be measured.

– 80 –

Page 80
Image 80
Toshiba RAV-SP1404AT8-E Temperature sensor, TA, TC, TCJ, TE, TS, to sensors Representative value, TD,TL sensors