9-3. Outdoor Unit

9-3. Outdoor Unit

9-3-1. Various Setting on Outdoor Unit (Existing piping, Power save, Cooling-only, etc.)

The following settings are available by DIP switch setup and jumper line setup.

Function

 

 

 

 

 

 

 

 

 

 

 

Set position

 

 

Control contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when mounting a duct to the discharge port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the outdoor unit. Add 3 taps to the upper limit value of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor fan tap.

 

 

 

 

 

 

 

 

 

High static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The operation is performed with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).

 

 

pressure setup

 

 

 

 

 

SW802

 

 

 

 

 

 

 

In this case, the upper limit value of static pressure for duct is 5Pa

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or less on 25°C degrees and please use straight duct.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this case, the outdoor noise level may increase.

 

 

 

 

 

 

1

 

2

 

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when Ø19.1 is used for the existing pipe.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High static pressure setup

In this case, the heating capacity may lower according to outside

piping setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing piping setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temp. and indoor temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power save setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power save

 

 

 

 

 

 

 

 

 

 

 

 

 

Snow-proof fan control

Turn the switch to ON when using the power save function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

all are OFF at shipment.

 

 

 

 

 

 

 

The control to lower the compressor frequency (Approx. –10%) is

setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

performed by indoor heat exchanger temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When snow enters from clearance of the fan guard or heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exchanger into blast path and it is accumulated, the control to

Snow-proof

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prevent generation of motor lock is validated.

 

 

 

 

fan control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When outside temp. is below 4°C though the compressor stops,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the outdoor fan operates with W5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost

 

 

 

 

 

 

 

 

 

 

 

J805, J806

The defrost interval is cut to shorten it than the standard status.

 

 

 

 

 

 

 

 

 

 

 

For contents of control and cutting method, refer to Section

 

 

time change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7-10. Defrost control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When it is needed to lower the maximum value of the compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency, cut the jumper line. Max. frequency at heating is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lowered.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this case the Max. capacity decreases.

 

 

 

 

 

Max. frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J807

Max. frequency of compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP110

SP140

SP160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

HEAT

COOL

HEAT

COOL

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard status

53.4

100.2

64.2

 

100.2

74.4

 

100.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When J807 is cut

53.4

69.6

64.2

 

75.0

74.4

 

79.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling-only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When using the air conditioner as a cooling-only conditioner, cut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J808

the jumper line. (An air conditioner can be changed to cooling-only

setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conditioner by “0F” of DN code on the remote controller.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 84 –