8-2-3. Monitor Function of Remote Controller Switch

nCalling of sensor temperature display

<Contents>

Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller.

<Procedure>

1 Push TEST + CL buttons simultaneously for 4 seconds to call the service monitor mode.

The service monitor goes on, the master indoor unit No. is displayed at first and then the temperature of CODE No. ￿￿ is displayed.

TEMP.

ON / OFF

ò

2 Push temperature set TEMP. buttons and then change the CODE No. of data to be monitored.

The CODE No. list is shown below.

 

 

TIMER SET

FAN

 

MODE

 

 

TIME

SAVE

 

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

1

3

<Operation procedure>

1 2 3 4

Returned to usual display

 

CODE No.

Data name

Unit

 

 

 

 

 

01

Room temperature

°C

 

 

(Remote controller)

 

data

02

Indoor suction temperature (TA)

°C

03

Indoor heat exchanger (Coil)

°C

 

temperature (TCJ)

 

unit

 

 

04

Indoor heat exchanger (Coil)

°C

Indoor

 

temperature (TC)

 

07

Indoor fan revolution frequency

rpm

F2

Indoor fan calculated operation time

×100h

 

 

F3

Filter sign time

×1h

 

F8

Indoor discharge temperature*1

°C

 

 

 

 

Outdoor unit data

CODE No.

Data name

Unit

 

 

 

60

Outdoor heat exchanger (Coil) temperature (TE)

°C

61

Outside temperature (TO)

°C

62

Compressor discharge temperature (TD)

°C

63

Compressor suction temperature (TS)

°C

65

Heat sink temperature (THS)

°C

6A

Operation current (× 1/10)

A

6D

Outdoor heat exchanger (Coil) temperature (TL)

°C

70

Compressor operation frequency

rps

72

Outdoor fan revolution frequency (Lower)

rpm

73

Outdoor fan revolution frequency (Upper)

rpm

F1

Compressor calculated operation time

×100h

 

 

 

The CODE No. with marks in the above table are displayed only on the indoor units of 4 series models and after.

(4 series indoor units mean RAV-SM1404UT-E for example.).

ò

3 Push UNIT LOUVER button to select the indoor unit to be monitored.

Each data of the indoor unit and its outdoor units can be monitored.

ò

4 Pushing TEST button returns the status to the usual display.

1 The indoor discharge temperature of CODE No. [F8] is the estimated value from TC or TCJ sensor.

Use this value to check discharge temperature at test run.

(A discharge temperature sensor is not provided to this model.)

• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.