3. Outdoor fan control

Revolution frequency allocation of fan taps [rpm]

 

 

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

SP110 to

Up

200

240

240

260

320

380

480

500

530

610

640

660

720

780

SP160

Down

200

280

360

400

500

520

550

630

660

700

740

820

3-1) Cooling fan control

The outdoor fan is controlled by TL sensor, TO sensor and the operation frequency. The outdoor fan is controlled by every 1 tap of DC fan control (14 taps).

Only for 60 seconds after the operation has started, the maximum fan tap corresponding to the zone in the following table is fixed and then the fan is controlled by temperature of TL sensor.

TL [˚C]

WE tap

 

58

 

55

 

 

+1 tap / 20 sec

 

Up to the maximum

 

revolution frequency of each zone

38

Revolution frequency hold

35

–1 tap / 20 sec

 

 

Up to the minimum

 

revolution frequency of each zone

3-2) Heating fan control

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

 

 

 

 

 

 

 

38°C TO

W6

WC

W8

WD

WA

WD

 

 

 

 

 

 

 

29°C TO < 38°C

W5

WB

W7

WC

W9

WC

 

 

 

 

 

 

 

15°C TO < 29°C

W4

W8

W6

WA

W8

WC

 

 

 

 

 

 

 

5°C TO < 15°C

W3

W6

W5

W8

W7

WA

 

 

 

 

 

 

 

0°C TO < 5°C

W2

W4

W4

W6

W5

W8

 

 

 

 

 

 

 

–4°C TO < 0°C

W2

W3

W3

W5

W4

W6

 

 

 

 

 

 

 

TO < –4°C

W1

W2

W1

W4

W2

W6

 

 

 

 

 

 

 

TO error

W1

WC

W1

WD

W2

WD

 

 

 

 

 

 

 

: WB for SP110

The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. (Control from minimum W1 to maximum (according to the following table))

For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in the following table is fixed and then the fan is controlled by temperature of TE sensor.

TE [˚C]

–2 taps / 20 sec. (Up to W1)

Stop timer count

24

–2 taps / 20 sec. (Up to W1)

21

–1 tap / 20 sec. (Up to W1)

18

Revolution frequency hold

15

+1 tap / 20 sec

(Up to the maximum tap of each zone)

Object: SP140 (SP160)

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

Max.

Max.

Max.

 

 

 

 

10°C TO

W7

W8

W9

 

 

 

 

5°C TO < 10°C

W9

WA

WB (WC)

 

 

 

 

–3°C TO < 5°C

WB (WC)

WB (WC)

WC

 

 

 

 

–10°C TO < –3°C

WC

WC

WC

 

 

 

 

TO < –10°C

WD

WD

WD

 

 

 

 

TO error

WD

WD

WD

 

 

 

 

ƒWhen TE 24°C continues for 5 minutes, the compressor stops.

It is the same status as the normal thermostat- OFF without error display.

The compressor restarts after approx. 2 minutes 30 seconds and this intermittent operation is not abnormal.

In case that the status in item ƒ generates frequently, stain on filter of the suction part of the indoor unit is considered.

Clean the filter and then restart the operation.

Object: SP110

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

Max.

Max.

Max.

 

 

 

 

10°C TO

W7

W8

W9

 

 

 

 

5°C TO < 10°C

W9

WA

WA

 

 

 

 

–3°C TO < 5°C

WA

WA

WC

 

 

 

 

–10°C TO < –3°C

WC

WC

WC

 

 

 

 

TO < –10°C

WD

WD

WD

 

 

 

 

TO error

WD

WD

WD

 

 

 

 