Toshiba RAV-SP1604AT8-E, RAV-SP1104AT8ZG-TR Accessory Parts And Refrigerant, 105, EN-8, 9-EN

Models: RAV-SP1404AT8Z-E RAV-SP1104AT8Z-E RAV-SP1404AT8ZG-E RAV-SP1404AT8-E RAV-SP1604AT8-TR RAV-SP1104AT8Z-TR RAV-SP1604AT8-E RAV-SP1404AT8-TR RAV-SP1604AT8Z-E RAV-SP1104AT8ZG-E RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-TR RAV-SP1104AT8-TR RAV-SP1104AT8ZG-TR

1 143
Download 143 pages 52.35 Kb
Page 105
Image 105
2 ACCESSORY PARTS AND REFRIGERANT

Super Digital Inverter

2 ACCESSORY PARTS AND REFRIGERANT

￿Accessory Parts

Part name

Q’ty

Shape

Usage

 

 

 

 

 

 

 

Hand this directly to the customer.

Outdoor unit installation manual

1

 

(For other languages that do not appear in this

 

Installation Manual, please refer to the enclosed

 

 

 

 

 

 

CD-R.)

 

 

 

 

Drain nipple

1

 

 

 

 

 

 

Waterproof rubber cap

5

 

 

 

 

 

 

Protective bush

1

 

For protecting wires (pipe cover)

 

 

 

 

Guard material for passage part

1

 

For protecting passage part (pipe cover)

 

 

 

 

Clamp filter

1

 

For conforming to EMC standards

 

(Used for power wire)

 

 

 

– 105 –

Super Digital Inverter

3 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER

The R410A refrigerant is more susceptible to impurities such as water, oxide membranes, oils, and fats. With the adoption of the new refrigerant, the refrigerating oil has also been changed.

Be careful not to let water, dust, conventional refrigerant, and/or conventional refrigerating oil enter the refrigerating cycle of the new refrigerant air conditioner.

To prevent different refrigerant or refrigerating oil from becoming mixed, the sizes of the charging port of the unit and the installation tool connection sections are different from those of the conventional refrigerant. Accordingly, the following exclusive tools are required for the new refrigerant R410A.

￿Required Tools/Equipment and Precautions for Use

Prepare the tools and equipment listed in the following table before starting the installation work.

Newly prepared tools and equipment must be used exclusively.

Legend

￿Accessory Parts : Prepared newly (Use for R410A only. Do not use for refrigerant R22 or R407C etc.) – 105 – : Conventional tools/equipment are available

Tools/equipment

Use

 

 

How to use tools/equipment

 

 

 

 

 

Gauge manifold

Vacuuming/charging refrigerant

 

 

Prepared newly for R410A only

 

 

 

 

 

 

 

 

Charging hose

and operation check

 

 

Prepared newly for R410A only

 

 

 

 

 

 

 

 

Charging cylinder

Can not be used

Unusable (Use the refrigerant charging measure

instead.)

 

 

 

 

 

 

 

Gas leak detector

Gas leak check

 

 

Prepared newly

 

 

 

 

 

Vacuum pump

Vacuum drying

Unusable

 

 

 

 

 

Vacuum pump with backflow

Vacuum drying

 

 

R22 (Conventional tools)

prevention function

 

 

 

 

 

 

 

 

 

 

 

Flare tool

Flare machining of pipes

 

 

Usable if dimensions are adjusted.

 

 

 

 

 

Bender

Bending pipes

 

 

R22 (Conventional tools)

 

 

 

 

 

Refrigerant recovery equipment

Refrigerant recovery

 

 

For R410A only

 

 

 

 

 

 

 

 

 

 

Torque wrench

Tightening flare nuts

 

 

Exclusive for Ø12.7 mm and Ø15.9 mm

 

 

 

 

 

 

 

 

 

 

Pipe cutter

Cutting pipes

 

 

R22 (Conventional tools)

 

 

 

 

 

Welding machine and nitrogen

Welding pipes

 

 

R22 (Conventional tools)

cylinder

 

 

 

 

 

 

 

 

 

 

 

Refrigerant charging measure

Charging refrigerant

 

 

R22 (Conventional tools)

 

 

 

 

 

EN-8

8

9

9-EN
Page 105
Image 105
Toshiba RAV-SP1604AT8-E Accessory Parts And Refrigerant, 105, Installation Of New Refrigerant Air Conditioner, EN-8, 9-EN