– 107 –
Super Digital Inverter
Installation Location
CAUTION
Install the outdoor unit in a location that meets the following conditions after the customer’s consent is obtained.
•A
•A location that is not exposed to rain or direct sunlight
•A location that does not increase the operating noise or vibration of the outdoor unit
•A location that does not produce any drainage problems from discharged water
Do not install the outdoor unit in the following locations.
•A location with a saline atmosphere (coastal area) or one that is full of sulfide gas
•A location subject to oil, vapor, oily smoke, or corrosive gases
•A location in which organic solvent is used
•A location where
•A location in which the discharged air of the outdoor unit blows against the window of a neighboring house
•A location where the operating noise of the outdoor unit is transmitted
•When the outdoor unit is installed in an elevated position, be sure to secure its feet.
•A location in which drain water poses any problems.
1. Install the outdoor unit in a location where the discharge air is not blocked.
2. When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building, secure normal fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper stairs or rooftop of a building, apply the windproofing measures referred to in the following examples.
1)Install the unit so that its discharge port faces the wall of the building.
Keep a distance 500 mm or more between the unit and wall surface.
500 mm
2)Consider the wind direction during the operational season of the air conditioner, and install the unit so
that sch arge port is set at a right angl e relative to the wind directio n.
Strong wind
Strong wind |
•When using an air conditione r der low outside
temperature conditions °C or lower) in COOL mode, prepare a duct or wind shield so that it is not affected by the wind.
•When installing the unit in an area where snowfalls may be heavy, take steps to prevent the unit from being adversely affected by the fallen or accumulated snow.
•Either make the foundation higher or install a stand (which is high enough to ensure that the unit will be above the fallen or accumulated snow) and place the unit on it.
•Attach a snow shi eld (locally procured).
<Example>
Wind (snow) shield | Widn (snow) shield |
Wind (snow) shield
Super Digital Inverter
Necessary Space for Installation (Unit: mm)
Obstacle at rear side
Upper side is free
1. Single unit installation
150 or more
2. Obstacles on both right and left sides
200or | more | The height of the |
lower than the height of | ||
|
| obstacle should be |
|
| the outdoor unit. |
150 or |
|
|
| 300 or |
more |
|
|
| more |
|
|
|
|
|
3. Serial installation of two or more units
200 or more
150 or | 300 or | 300 or | 300 or |
more | more | more | more |
The height of the obstacle should be lower than the height of the outdoor unit.
Obstacle also above unit |
| |
500 or | more | 150 or |
more | ||
|
Obstacle in front
Above unit is free
1. Single unit installation
500 or more
2. Serial installation of two or more units
1,000 or more
Obstacle also at the above unit |
|
|
1,000 or | 1,000or | more |
more |
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
150 or | more |
1,000 or | more |
2. Serial installation of two or more units
|
| 200 or | more |
300 or | 300 or | 1,000or | more |
more | more |
| 12 | 13 |
|