Toshiba RAV-SP1604AT8-TR 107, Installation Location, Necessary Space for Installation Unit mm

Models: RAV-SP1404AT8Z-E RAV-SP1104AT8Z-E RAV-SP1404AT8ZG-E RAV-SP1404AT8-E RAV-SP1604AT8-TR RAV-SP1104AT8Z-TR RAV-SP1604AT8-E RAV-SP1404AT8-TR RAV-SP1604AT8Z-E RAV-SP1104AT8ZG-E RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-TR RAV-SP1104AT8-TR RAV-SP1104AT8ZG-TR

1 143
Download 143 pages 52.35 Kb
Page 107
Image 107
– 107 –

– 107 –

Super Digital Inverter

￿Installation Location

CAUTION

Install the outdoor unit in a location that meets the following conditions after the customer’s consent is obtained.

A well-ventilated location free from obstacles near the air inlets and air outlet

A location that is not exposed to rain or direct sunlight

A location that does not increase the operating noise or vibration of the outdoor unit

A location that does not produce any drainage problems from discharged water

Do not install the outdoor unit in the following locations.

A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area) (Special maintenance is required.)

A location subject to oil, vapor, oily smoke, or corrosive gases

A location in which organic solvent is used

A location where high-frequency equipment (including inverter equipment, private power generator, medical equipment, and communication equipment) is used (Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due to noise from such equipment.)

A location in which the discharged air of the outdoor unit blows against the window of a neighboring house

A location where the operating noise of the outdoor unit is transmitted

When the outdoor unit is installed in an elevated position, be sure to secure its feet.

A location in which drain water poses any problems.

1. Install the outdoor unit in a location where the discharge air is not blocked.

2. When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building, secure normal fan operation by using a duct or wind shield.

3. When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper stairs or rooftop of a building, apply the windproofing measures referred to in the following examples.

1)Install the unit so that its discharge port faces the wall of the building.

Keep a distance 500 mm or more between the unit and wall surface.

500 mm

2)Consider the wind direction during the operational season of the air conditioner, and install the unit so

that ￿Installation Location sch arge port is set at a right angl e relative to the wind directio n.

Strong wind

Strong wind

When using an air conditione r ￿Necessary Space for Installation (Unit: mm)der low outside

temperature conditions EN-1213-ENManual background °C or lower) in COOL mode, prepare a duct or wind shield so that it is not affected by the wind.

When installing the unit in an area where snowfalls may be heavy, take steps to prevent the unit from being adversely affected by the fallen or accumulated snow.

Either make the foundation higher or install a stand (which is high enough to ensure that the unit will be above the fallen or accumulated snow) and place the unit on it.

Attach a snow shi eld (locally procured).

<Example>

Wind (snow) shield

Widn (snow) shield

Wind (snow) shield

Super Digital Inverter

￿Necessary Space for Installation (Unit: mm)

Obstacle at rear side

Upper side is free

1. Single unit installation

150 or more

2. Obstacles on both right and left sides

200or

more

The height of the

lower than the height of

 

 

obstacle should be

 

 

the outdoor unit.

150 or

 

 

 

300 or

more

 

 

 

more

 

 

 

 

 

3. Serial installation of two or more units

200 or more

150 or

300 or

300 or

300 or

more

more

more

more

The height of the obstacle should be lower than the height of the outdoor unit.

Obstacle also above unit

 

500 or

more

150 or

more

 

Obstacle in front

Above unit is free

1. Single unit installation

500 or more

2. Serial installation of two or more units

1,000 or more

Obstacle also at the above unit

 

 

1,000 or

1,000or

more

more

Obstacles in both front and rear of unit

Open above and to the right and left of the unit.

The height of an obstacle in both the front and rear of the unit, should be lower than the height of the outdoor unit.

Standard installation

1. Single unit installation

150 or

more

1,000 or

more

2. Serial installation of two or more units

 

 

200 or

more

300 or

300 or

1,000or

more

more

more

EN-12

12

13

13-EN

Page 107
Image 107
Toshiba RAV-SP1604AT8-TR service manual 107, Installation Location, Necessary Space for Installation Unit mm, EN-12, 13-EN