Toshiba RAV-SP1404AT8ZG-E, RAV-SP1104AT8-TR 81, Parts name, Checking procedure, Resistance value

Models: RAV-SP1404AT8Z-E RAV-SP1104AT8Z-E RAV-SP1404AT8ZG-E RAV-SP1404AT8-E RAV-SP1604AT8-TR RAV-SP1104AT8Z-TR RAV-SP1604AT8-E RAV-SP1404AT8-TR RAV-SP1604AT8Z-E RAV-SP1104AT8ZG-E RAV-SP1404AT8Z-TR RAV-SP1404AT8ZG-TR RAV-SP1104AT8-TR RAV-SP1104AT8ZG-TR

1 143
Download 143 pages 52.35 Kb
Page 81
Image 81
Parts name

Table Inspection of outdoor unit main parts

No.

Parts name

 

 

Checking procedure

 

 

 

 

 

1

Compressor

Measure the resistance value of each winding by using the tester.

 

(Model : DA422A3F-27M)

 

Red

 

 

 

 

 

 

 

Position

Resistance value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red – White

 

 

 

 

 

 

 

 

 

 

 

 

White

Black

 

White – Black

0.79 ± 0.04 Ω

 

 

 

 

 

 

 

 

 

 

Black – Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Under 20°C

 

 

 

2

Outdoor fan motor

Measure the resistance value of each winding by using the tester.

 

(Model : ICF-280-A100-1)

 

Red

 

 

 

 

 

 

 

Position

Resistance value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red – White

 

 

 

 

 

 

 

 

 

 

 

 

White

Black

 

White – Black

14.8 ± 1.5 Ω

 

 

 

 

 

 

 

 

 

 

Black – Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Under 20°C

 

 

 

3

4-way valve coil

Measure the resistance value of each winding by using the tester.

 

(Cooling/heating switching)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Model : STF-01AJ502E1)

 

 

 

Resistance value

 

 

 

 

 

 

 

 

 

 

 

 

 

1435 ± 144 Ω

 

 

 

 

Connector : White

 

 

 

 

 

 

 

 

 

Under 20°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 81 –

Page 81
Image 81
Toshiba RAV-SP1404AT8ZG-E, RAV-SP1104AT8ZG-TR, RAV-SP1104AT8-TR 81, Parts name, Checking procedure, Resistance value